BAMOSOFT Control Bamo Water Hardness Monitor

BAMOSOFT Control Bamo Water Hardness Monitor monitors safely the quality of softened water. It emits a light alarm as soon as the hardness of the outlet water is near or above the threshold. (See the signaling table)

Example: Raw water (tap water): hardness of 300 ppm CaCO₃ Threshold is set at 0.25 %: for alarming when the hardness of softened water is above 0.25 % of raw water hardness. It means that an alarm occurs when softened water hardness is over 0.75 ppm of CaCO₃.

BAMOSOFT Control also delivers a 4-20 mA signal which represents the percentage of residual hardness in the softened water, in comparison to raw water hardness.

Example: Raw water hardness (tap water) is 300 ppm CaCO₃. Output signal 4-20 mA is set on the scale 0 … 2 %. The value 20 mA will represent 2% of raw water hardness, here: 6 ppm CaCO₃.

BAMOSOFT Control Operation

BAMOSOFT Control comprises two solenoid valves that successively pass raw water and then softened water on a specific Ca⁺⁺ /Mg⁺⁺ electrode. With its hardware, the analyzer contemplates the ionic activities, compares data and proceeds to check the system, less or more frequently. The controller delivers information: normal operation, alarm, faulty solenoid valve, brine leakage, etc.

Water samples are rejected to drain (no pressure). After start-up, once measurements are stabilized, BAMOSOFT triggers a sampling routine each 15 minutes. It is possible to trigger sampling by an external signal (counter with pulse, external contact).

Signaling table of LEDs

Bamo Water Hardness Monitor Depending on their meanings, they turn on “continuous or flashing. In the table below, S stands for “Threshold set”.

Features

  • Fit any water softener system
  • On-line control and monitoring
  • Alarm set up from 0.25% to 10% of raw water hardness
  • Self diagnostic of complete system
  • Signal outputs for remote information

Application

Control and monitoring of softened water quality, by comparison of waters from softener inlet and outlet.

BAMOSOFT Control Specification

Water temperatureWater: 5 … 30 °C; Ambient: 5 … 50 °C
%R.H.20 … 80 % RH
Power Unit100 … 240 V – 50/60 Hz / 0.2 A
Output delivered voltage15 V DC; approx. 6 W
Relay output2 Change-over contacts; max. 24 V DC / 0.5 A
Relay 1: Threshold over-passed or brine detected
Relay 2: Electrode fault or Solenoïd valve fault
Fittings for samplesBy-pass with fittings for PA tube
PA tube: O.D. 4 mm, i.d. 2 mm ; In-line filter < 0.1 mm is highly recommended
Samples pressure limitsMin. 1 bar; Max. 7 bar
Outlet to drainPA Tube, O.D. 6 mm; No pressure
Raw water qualityDrinkable quality, free of grease, oil and brine
RestrictionsConcentration of iron and manganese less than 0.05 mg/l (More information: Contact us)
Hardness range10 to 1000 ppm CaCO₃
Trigger point8 Thresholds in % of raw water hardness: 0.25 ; 0.5 ; 1 ; 2 ; 4 ; 6 ; 8 or 10 %
Analogue output signal4-20 mA (max. 250 Ω) – Scales 0 … 2% or 0 … 10% of raw water hardness
Electrode check-upSelf-diagnostic with alarm for low effectiveness
External sampling signalPulse limit > 0.5 s
DimensionsWall mounting; Case: 95 x 145 x 35 mm (Overall 120 x 220 x 120 mm)

Download Data Sheet: Water Hardness Monitor BAMOSOFT Control