Pulsar Quantum 2 Superior Pumping Station Control

About the Quantum2

The Quantum2 is a state-of-the-art pump management, and level controller, that provides advanced operating routines suitable for an extremely wide variety of applications. The system combines premium specifications with
high performance even in the most arduous applications where high turbulence and foam or froth is present.

General Information

Quantum 2 by Pulsar Measurement is designed to be an intelligent and sophisticated pump controller. Featuring unique intelligent pumping, with ‘time to spill’ alarms and DATEM echo discrimination to provide solid performance and sophisticated level measurement.

The unit has the ability to reset pumps automatically and can be used in those high-risk areas to enhance site management. Featuring a large onboard data logging facility, it enables the entire pump station process to be transparent.

Quantum 2 Intelligent Pump Controller features 10 relays (digital outputs) and 7 digital inputs, with the option to add RS485 digital communications, allowing for the status of the operation to be monitored and the unit to be programmed remotely.

Description

Pulsar Quantum 2 Superior Pumping Station Control is a fully-featured pump controller, uses Pulsar’s non-contacting ultrasonic technology including DATEM digital echo discrimination to provide solid performance and sophisticated level management.

Quantum 2 includes 10 relays (digital outputs) and 7 digital inputs and has optional RS485 digital communications (Modbus and optional Profibus DP V0 and V1) allowing the status to be monitored and the unit to be programmed remotely. Additionally, Quantum 2 has the option of a large onboard data-logging facility (256kb).

Functional Description

The Quantum2 level and pump controller is a highly developed ultrasonic level measurement system that provides non-contacting sophisticated pump and level control routines suitable for an extremely wide variety of applications.

Easy calibration and maintenance-free “fit and forget” performance mean that you can install the Quantum2 pump controller rapidly and with confidence. Ten user-definable relays with adjustable, individual on and off points. Seven user-definable digital inputs, 2 x isolated mA output, RS 232, and intelligent performance logging software features provide the user with a superior pump management system and comprehensive level measurement information.

The Quantum2 operates on the principle of timing the echo received from a measured pulse of sound transmitted in air and utilizes the unique DATEM software (Digital Adaptive Tracking of Echo Movement).

Pulsar Quantum 2 Features

  • Highly intelligent pump controllers
  • Time to spill calculation and warning
  • Automatically resets tripped pumps
  • Second mA output for pumped flow rate
  • Easy prompt led set up
  • RS485 Modbus and Profibus DP V0 and V1 options
  • 10 relay outputs and 7 digital inputs
  • Pump efficiency alarm function
  • Peak power tariff avoidance
  • This unit can also be configured using Pulsar’s PC Suite software

Applications

  • Pump Control
  • Time to spill warning requirements
  • Reduction in power cost requirements
  • Pump monitoring and control
  • Water and waste water

Component Units

Power

The Quantum2 can operate from mains AC and automatically from DC or battery backup in the event of power failure or can be operated permanently from DC or batteries.

Transducer(s)

The transducer should be installed, and connected, in accordance with the installation instructions contained in the Transducer User Guide. Wire the transducer to the Quantum2 ’s transducer terminals, as follows:

Display

The display provides information on the current mode of operation and the status of the remote communication. Whilst in the Run Mode it will display the current level reading and its units of measure, along with status messages with regards to the Transducer, Echo reception and Fail Safe Mode. Additionally, it can be programmed to provide status messages on alarms, pumps etc.

When in the Program mode the display is used to read the information on the Menu System, Parameter Number and parameter details and values, which can be entered. During Test Mode, the display is used to monitor the simulated level. A bar graph is also provided which will provide a visual reading of the level, in the percentage of span.

Hot Keys

There are five hot keys on the keypad, which can be used to quickly access common parameters for viewing only, while in Run Mode. Pressing the hot key once will display the first parameter, then repeated pressing will display
the others, then the Quantum2 reverts to Run Mode. In program mode, they have different functions, the functions are shown below.

Pulsar Quantum 2 Specifications

Physical

Mounting option:Fascia Mount
Sensor Body Dimensions:200 x 112mm (7.87 x 4.41in) front, 165 x 105mm (6.49 x 4.13in) cut-out
Weight:Nominal 1.3kg (2.9lbs)
Transducer cable:Twin Screened
Maximum Separation:1000m (3280ft)
Case Material:Stainless steel and polycarbonate, flame resistant to UL94 V0

Environmental

IP Rating:IP64
Max. and Min. Temperature (electronics):-20C to +55C (-4F to +131F)
Flammable atmosphere approval:Safe area: compatible with approved dB transducers allowing installation to zone 0
CE Approval:See EC Declaration of Conformity in the manual
UL/C-UL:UL Listed. UL Listed to Canadian safety standards. Certificate Number: E257330
Power Supply:115V ac +5%/ -10% 50/60Hz, 220V ac +5%/ -10%, 18-36V dc

Power Supply Requirements

The Quantum2 can operate from AC supply or from a DC battery. The AC is either 115V+5%/-10% 50/60Hz or 230V +5%/-10% 50/60Hz, depending on the position of the selector switch. The DC is 18-36V. In all cases, the Quantum2 will typically consume 6W of power, with a maximum of 10W.Performance

Accuracy:+0.25% of the measured range or 6mm whichever is greater
Resolution:dBMACH3 0.25mm, dB3 0.5mm, dB6 and dB10 1mm, dB15 1.5mm, db25 2.5mm, dB40 5mm
Range:Depending upon the transducer, from 125mm to 40m (0.41-130ft)
Echo Processing:Patented DATEM (Digital Active Tracking of Echo Movement)
Digital Communications:RS485 Modbus or Profibus DP V0 or V1

Outputs/Inputs

Volt-free contacts:10 in total. Relays 1-5 form C (SPDT 5A, 220V ac. Relays 6-10 form C (SPDT) 3A, 220V ac
Digital Inputs:7 No or NC with 24V dc internal supply, available max. 20mA
Analogue output (adjustable):2 off Isolated output of 4-20mA or 0-20mA into 500Ω (user programmable and adjustable) 0.1% resolution
Analogue input:Isolated input for loop powered device. 4-20mA source. NB: Active input on request
Serial Output:RS232 via RJ11 port
Display:6 digits plus 12 character text, plus bargraph with direction indicators, remote communicator idintifier and program/run/test mode indicators

Programming

On-Board Programming:Standard with integral keypad
PC Programming:Via RS232 (RJ11 port)
Programming Security:Via password (user selectable and adjustable)
Programmed Data Integrity:Via non-volatile RAM, plus backup

Download Datasheet: Quantum 2 Pulsar Superior Pumping Station Control

Reference: pulsar.pm

Another Article:

Similar Posts

Discover more from Indonesia Industrial Parts

Subscribe now to keep reading and get access to the full archive.

Continue reading