Categories: Electrical Parts

Weidmuller ACT20C Network-compatible Current Measuring Transducers

The Weidmuller ACT20C series was especially developed for applications with continuous processes. It enables the continuous monitoring of diagnostic, device and process information (“condition monitoring”). Several ACT20C components form a station which consists of an ACT20C Ethernet gateway, communicative ACT20C signal converters and an ACT20C bus termination terminal.

Specifications

Technical Data

Dimensions and weights

  • Height : 117.2 mm
  • Width : 22.5 mm
  • Depth : 113.6 mm
  • Height (inches) : 4.614 inch
  • Width (inches) : 0.886 inch
  • Depth (inches) : 4.472 inch
  • Net weight : 150 g

Temperatures

  • Humidity : 5…95 %, no condensation
  • Operating temperature : min. -25 °C
  • Storage temperature : min. -40 °C
  • Ambient temperature : -25 °C…+60 °C
  • Operating temperature : max. 60 °C
  • Storage temperature : max. 85 °C
  • Operating temperature : -20 °C…70 °C
  • Storage temperature : -40 °C…85 °C

Probability of failure

  • MTTF : 160 Years

Environmental Product Compliance 

  • REACH SVHC : Lead 7439-92-1

Communication

  • Addressing
    DHCP or manual adjustment
  • Configuration
    With FDT/DTM software, DHCP
  • Interface
    Ethernet 10/100 Base T, Jack plug for CBX200, Communication via CH20M rail bus with all current measuring transducers (ACT20CCMT-x)
  • Protocol
    Modbus/TCP, DHCP Server/Client
  • RJ45 ports
    10/100BaseT(X), auto negotiation

Input

  • Type : receives data via the CH20M rail bus from several ACT20C-CMT communicative currentmeasuring transducers.

General data

  • Configuration
    With FDT/DTM software, DHCP
  • Power consumption
    1.5 W
  • Rail
    TS 35
  • Voltage supply
    18.0 … 31.2 V DC

Insulation coordination

  • EMC standards
    IEC 61326-1
  • Pollution severity
    2
  • Impulse withstand voltage
    0,5 kV (1.2/50 μs)
  • Surge voltage category
    II
  • Rated voltage ⁄ test voltage: Ethernet interface to supply ⁄ functional earth to Supply ⁄ Ethernet interface
    30 V AC RMS

Connection data 

  • Type of connection : Screw connection/ RJ45 plug-in connector
  • Tightening torque, min : 0.5 Nm
  • Tightening torque, max : 3.5 Lb In
  • Clamping range, rated connection : 1.5 mm²
  • Clamping range, min. : 0.5 mm²
  • Clamping range, max. : 2.5 mm²
  • Wire connection cross section AWG, min. : AWG 30
  • Wire connection cross section AWG, max. : AWG 14
  • Wire cross-section, solid, min. : 0.5 mm²
  • Wire cross-section, solid, max. : 2.5 mm²
  • Wire connection cross-section, finely stranded, min. : 0.5 mm²
  • Wire connection cross section, finely stranded, max. : 2.5 mm²

Classifications

  • ETIM 6.0 : EC002475
  • ETIM 7.0 : EC002475
  • eClass 9.0 : 27-21-01-23
  • eClass 9.1 : 27-21-01-23
  • eClass 10.0 : 27-21-01-23

Approvals

  • EAC
  • DNVGL
  • UL
  • ROHS : Conform

Download : Weidmuller ACT20C Network-compatible Current Measuring Transducers