Omron E8Y Differential Pressure Sensor

Descriptions

Pressure Sensors detect the pressure of liquids and gases, and Flow Sensors detect the flow rate of liquids. OMRON Sensing Components detect, measure, analyze, and process various changes that occur on productions sites, such as changes in position, length, height, displacement, and appearance. They also contribute to predicting and preventing future events.

Features and Benefits

  • Repeat accuracy of ±1% FS (setting resolution: 01 kPa), high-precision pressure control available.
  • Compact design (31 ´ 30 ´ 30 mm) saves mounting
  • Easy-to-read red LED
  • Analog current output models available (E8Y-A@Y).
  • Pressure port Rc (PT) 1/8 models available (-R).

Ratings

Model Item E8Y-AR2C E8Y-AR5C E8Y-A2C E8Y-A2C-R E8Y-A5B E8Y-A5C E8Y-A5C-R E8Y-AR2Y E8Y-A2Y E8Y-A2Y-R E8Y-A5Y E8Y-A5Y-R
Power supply voltage 12 to 24 VDC ±10% with a ripple (p-p) of 10% max.
Current consumption 50 mA max. 75 mA max.
Pressure type Differential pressure
Rated pressure range 0 to 200 Pa 0 to 500 Pa 0 to 2.00 kPa 0 to 5.00 kPa 0 to 200 Pa 0 to 2.00 kPa 0 to 5.00 kPa
Withstand pressure 5 kPa 50 kPa 5 kPa 5 kPa
Applicable fluid Non-corrosive gas and non-flammable gas
Output current 4 to 20 mA
Permissible load resistance —- 0 to 250 W
Precision ±2.5%FS ±1.0%FS
Linear output Linearity ±2.5%FS ±1.0%FS
Output form NPN open collector (NO/NC) *
Load current 100 mA
Output applied voltage 30 VDC max.
Residual voltage 1.0 V max. with a load current of 100 mA or 0.4 V max. with a load current of 16 mA
Digital output Repeat accuracy ±2.5%FS ±1.0%FS ±2.5%FS ±1.0%FS
Dis- play Display 3-digit 7-segment red LED
Indicator lamp Orange LED indicator (OUT1: lit when digital output is ON) Orange LED indicator (OUT2: lit when digital output is ON)
Response speed 0.5 s max.
Display accuracy ±1.0%FS
Setting resolution 1 Pa 0.01 kPa 1 Pa 0.01 kPa
Protection circuits Reverse polarity protection, load short-circuit protection
Ambient temperature Operating: -10 to 55°C (with no icing)
Ambient humidity Operating: 25% to 85% (with no condensation)
Storage temperature -25 to 65°C
Accessories Mounting Brackets (A and B), Instruction manual

Specifications

Temperature influence E8Y-A2C/A5C: ±3%FS max. E8Y-AR5C: ±6%FS max. E8Y-AR2C: ±10%FS max.
Humidity influence E8Y-A2C/A5C: ±3%FS max. E8Y-AR5C: ±6%FS max. E8Y-AR2C: ±10%FS max.
Degree of protection IP40 (IEC)
Dielectric strength 1,000 VAC at 50/60 Hz for 1 minute
Insulation resistance 100 MW min. (at 500 VDC) between current-carrying parts and case
Vibration resistance Destruction: 10 to 150 Hz, 0.75-mm single amplitude or 100 m/s2, 4 times each for 8 min in X, Y and Z directions
Shock resistance Destruction: 300 m/s2 3 times each in X, Y and Z directions
Pressure port 4.5-dia resin pipe or Rc (PT) 1/8 taper screw (-R type)
Cable Vinyl-insulated round cable 4 dia., Standard length: 2 m
Weight Approx. 80 g

Ref: Omron.co.id