Hengesbach TPF 200/201 Pressure and Level Transmitter

The  Hengesbach TPF 200/201 Level and pressure transmitters are suitable for taking pressure and filling level measurements in pipelines and containers. The wide range of hygienic process connections enables use in all applications in the food and pharmaceutical industries.

The vacuum-proof measuring cell with stainless steel membrane works on the basis of the piezoresistive measuring principle The TPF pressure transmitters are designed to measure from -1/0…0.35 to -1/0…100bar. Special measuring ranges are also available on request. Given the nature of the design for long-term medium temperatures of up to 125°C / 200°C, CIP and SIP cleaning methods can be used on the transmitters. The high protection classes of IP67 and IP69K also mean that the devices can be safely cleaned on the outside with foam and a high-pressure cleaner and that moisture is reliably prevented from entering the device.

The TPF pressure transmitters are suitable for taking pressure and filling level measurements in pipelines and containers. The wide range of hygienic process connections enables use in all applications in the food and pharmaceutical industries. Customer-specific process connections are also possible on request.

The vacuum-proof measuring cell with stainless steel membrane works on the basis of the piezoresistive measuring principle The TPF pressure transmitters are designed to measure from -1/0…0.35 to -1/0…100bar. Special measuring ranges are also available on request. Given the nature of the design for long-term medium temperatures of up to 125°C / 200°C, CIP and SIP cleaning methods can be used on the transmitters. The high protection classes of IP67 and IP69K also mean that the devices can be safely cleaned on the outside with foam and high-pressure cleaners and that moisture is reliably prevented from entering the device. For additional protection against moisture, the electronics are fully encapsulated in the housing.

Features:

  • High precision 0.05% fs, turn down 10, vacuum safe
  • Wide range of process connections for hygienic applications
  • Optional with hart®-protocol
  • Tank linearisation for standard tank shapes and special designs thanks to volumetric measurement
  • Diagnosis function for monitoring of devices
  • Copying of device parameters with easy transfer
  • Application strengths: measurement of content of pressurized tanks/vacuum measurements with high temperatures

Specification:

General details
Device type / measuring principleTPF 200/201/200H/201H: piezoresistive
Input
Measuring rangesTPF 200/201/200H/201HTPF 200/201/200H/201H
Standard nominal measuring ranges [bar]relativeOPabsoluteOP
OP = overload protection [bar]0…0.351
0…130…13
-1/0…2.580…2.58
Special measuring ranges-1/0…5150…515
-1/0…10300…1030
All measuring cells are vacuum-proof-1/0…30900…3090
-1/0…1002500…100250
Setting the measuring rangesVia the keypad of the OPUSi display and operating module / via the integrated on-site display Optional: via HART®
Setting rangesStart the measuringzero:0…90%of the sensor’s nominal measuring span
Measuring span span:10…100%of the sensor’s nominal measuring span
Burst pressure DIN16086≥ 4-fold measuring range
Output
Output signal2-wire:   4…20mA with a test circuit connection in the device
Optional: 4…20mA HART®
Fault signalOptional: 3.8mA, 22mA, hold (i.e. holding the last value)
Current limitation3.85mA and 21.5mA (normal operation)
Integration timeContinuously selectable between 0 and 300s (setting time after a pressure leap)
Measuring accuracy
Reference conditionsacc. to DIN IEC 770
Linearity, hysteresis and repeatability as per the limit point method DIN IEC 770≤ ± 0.05% of the sensor’s nominal measuring range
Activation time< 5s (the device will carry out a self-test.)
Setting time (without damping)< 200ms
Long-time drift≤ 0.2% of the span per year
Thermal hysteresis≤ ± 0.75% beginning of the measuring range / ≤ ± 0.8% end of the measuring range (VRM)
≤ ± 0.2% of the sensor’s nominal measuring range / 10K (-20…+80°C) from 4 bar (PZM)
≤ ± 0.3% of the sensor’s nominal measuring range / 10K (-20…+80°C) up to 0.6 bar (PZM)
Conditions of use
Installation position / calibration positionAny position / standing vertically (position-dependent zero point displacement)
Medium temperatureT1: -40…+125°C (140°C over one hour at the most)
T2: -40…+200°C (high-temperature version)
Ambient storage temperatureType 201/201H:-40…+85°C
Type 200/200H:-30…+75°C
(Below -20°C cable breakage might occur and the display’s function may be impaired.)
Protection class acc. to EN60529IP 67 and IP 69K
Electromagnetic compatibilitySensitivity against interference: acc. to DIN IEC 61000-6-2
Interference radiation:acc. to DIN IEC 61000-6-4
Construction
Electrical connection– Standard: cable screw connection M16x1.5, nickel-plated brass, stainless steel available on request
– Optional: round plug-in connector M12x1, nickel-plated brass, stainless steel available on request
– Optional: angle plug acc. to EN 175301-803
– Optional: reference cable
Process connection– All standard front-mounted process connections and those that are commonly used by the manufacturer
– Membrane, flush-welded on the front, CrNiSt, other materials available on request

Download Data Sheet: Pressure and Level Transmitter TPF 200/201

Ref: hengesbach.com