Description
Greystone TNAP Temperature Sensor utilizes a precision sensor encapsulated in a 6 mm (0.236”) OD, 304 series stainless steel probe and is available in various lengths (see ordering chart). All probes provide excellent heat transfer, fast response and resistance to moisture penetration. The transmitter provides a BACnet® or Modbus signal for network connection. A compact ABS enclosure with a hinged and gasketed cover is provided for ease of installation.
The duct type probes are installed through a hole in the side of the duct to monitor a single point temperature within the duct. Since the probes are tip sensitive, select a probe length that places the sensor well into the duct. Install the probe in a straight section of duct at a suitable distance downstream from any heating, cooling, or humidification devices.
PRODUCT DESCRIPTION
The all purpose single point network temperature sensor utilizes a precision sensor encapsulated in a 6 mm (0.236”) OD, 304 series stainless steel probe and is available in various lengths. All probes provide excellent heat transfer, fast response and resistance to moisture penetration. The transmitter provides a BACnet® or Modbus signal for network connection. A compact ABS enclosure with a hinged and gasketed cover is provided for ease of installation.
TYPICAL INSTALLATION
For complete installation and wiring details, please refer to the product installation instructions. The duct type probes are installed through a hole in the side of the duct to monitor a single point temperature within the duct. Since the probes are tip sensitive, select a probe length that places the sensor well into the duct. Install the probe in a straight section of duct at a suitable distance downstream
from any heating, cooling, or humidification devices. The enclosure provides mounting tabs for ease of installation.
NOTE: For immersion applications, T2 series thermowell is required. When using a T1 series thermowell an adapter will be required (#0201001092).
Greystone TNAP Temperature Sensor Future
- Precision RTD sensing element
- High Accuracy Transmitter
- BACnet® or Modbus Communication
- Compact ABS Enclosure
SPECIFICATIONS
- POWER SUPPLY BACnet® :
- 24 Vac/dc ±10% (non-isolated half-wave rectified)
- Modbus: 24 Vac/dc ±20% (non-isolated half-wave rectified
- CONSUMPTION BACnet®:
- 25 mA max @ 24 Vdc
- Modbus: 10 mA max @ 24 Vdc
- OPERATING ENVIRONMENT -40 to 50°C (-40 to 122°F), 5 to 95 %RH non-condensing
- PROBE MATERIAL 304 series stainless steel
- PROBE DIAMETER 6 mm (0.236”)
- STANDARD LENGTHS
- 50, 100, 150, 200, 300, and 450 mm
- (2”, 4”, 6”, 8”, 12”, and 18”)
- WIRING CONNECTIONS
- Screw terminal block (14 to 22 AWG)
- ENCLOSURE
- A: ABS, UL94-V0, IP65 (NEMA 4X)
- E: Same as A, with thread adapter (1/2” NPT to M16) and cable gland fitting
- TEMPERATURE Sensing Element: NTC thermistor
- Accuracy: ±0.2°C (±0.36°F) @ 0 to 70°C (32 to 158°F)
- Probe Sensing Range: -40 to 100°C (-40 to 212°F)
- Resolution: 0.1°C/°F
- BACnet® COMMUNICATIONS INTERFACE Hardware:
- 2 wire RS-485
- Software: Native BACnet® MS/TP protocol
- Baud Rate: 9600, 19200, 38400, 57600, 76800, or 115200 (auto-detect)
- Network Address Range: Locally set to 0-127
- Serial Configuration: 8N1
- MODBUS COMMUNICATIONS INTERFACE Hardware:
- 2 wire RS-485
- Software: Native Modbus MS/TP protocol (RTU)
- Baud Rate: 9600, 19200, 38400, 57600, 76800, or 115200 (auto-detect)
- Network Address Range: Locally set to 1-255 (switch selectable)
- Parity: None
- Stop Bits: 1
- Error Checking: A001 (CRC-16 revers
- INPUT VOLTAGE EFFECT Negligble over specified operating range
- PROTECTION CIRCUITRY Reverse voltage protected and transient protected