Pressure and Level Transmitter PZT 200/201 Hengesbach

The PZT pressure transmitters are suitable for taking pressure and filling level measurements in pipelines and containers. The modular process connection system offers a wide range of connection adapters and helps to cut costs in the long term. The flush-mounted process connection with an elastomer-free sealing cone is predestined for measurements that satisfy even the most stringent hygiene requirements.

The vacuum-proof measuring cell with stainless steel membrane works on the basis of the piezoresistive measuring principle The PZT pressure transmitters are designed to measure from -1/0…0.35 to -1/0…100bar. Special measuring ranges are also available on request. Given the nature of the design for long-term medium temperatures of up to 125°C / 200°C, CIP and SIP cleaning methods can be used on the transmitters.

The high protection classes of IP67 and IP69K also mean that the devices can be safely cleaned on the outside with foam and a high-pressure cleaner and that moisture is reliably prevented from entering the device.

All the pressure transmitters in series 200/201are highly precise and have been developed for difficult tank content measurements and, in particular, for applications with constantly high temperatures of up to 200°C. Furthermore, using the on-site display with series 200 and the display and operating module OPUS I in series 201, the pressure transmitters can be simply read out, configured, and diagnosed. With the EASY TRANSFER function, the configuration data can be copied via the OPUSi module onto other pressure transmitters in series 201. This makes commissioning easier for the same applications. The option of programming in tank dimensions for standard tank designs as well as for special tanks using the volumes calculated by means of volumetric measurement means exact filling levels and tank content can be shown directly. In addition to the features of the 200/201 series, the pressure transmitters in the 200H/201H series boast an integrated HART®
modem. This also enables remote configuration and evaluation of the transmitters using the HART® protocol.

Electrical Connection: The standard electrical connection is via a cable screw connection M16x1.5. On removing the device lid, the connection is created using screw terminals.

Features:

  • Modular process connection system with elastomer-free sealing cone
  • High precision 0.05% fs, turn down 10, vacuum safe
  • Optional with hart®protocol
  • Tank linearisation for standard tank shapes and special designs thanks to volumetric measurement
  • Diagnosis function for monitoring of devices
  • Copying of device parameters with easy transfer
  • Application strengths: measurement of the content of pressurized tanks/vacuum measurements with high temperatures

Specification:

General details
Device type / measuring principlePIEZOTEC PZT 200/201/200H/201H: piezoresistive
Input
Measuring rangesPZT 200/201/200H/201H
Standard nominal measuring ranges [bar]relativeOPabsoluteOP
OP = overload protection [bar]0…0.351
0…130…13
-1/0…2.580…2.58
-1/0…5150…515
-1/0…10300…1030
-1/0…30900…3090
-1/0…1002500…100250
Setting the measuring rangesVia the keypad of the OPUSi display and operating module / via the integrated on-site display Optional: via HART®
Setting rangesStart the measuring zero:0 to 90% of the sensor’s nominal measuring spanTD=10
Measuring span span:10 to 100% of the sensor’s nominal measuring span
Burst pressure DIN16086? 4-fold measuring range
Output
Output signal2-wire:   4…20mA with a test circuit connection in the device
Optional: 4…20mA HART®
Fault signalOptional: 3.8mA, 22mA, hold (i.e. holding the last value)
Current limitation3.85mA and 21.5mA (normal operation)
Integration timeContinuously selectable between 0 and 300 s (setting time after a pressure leap)
Measuring accuracy
Reference conditionsacc. to DIN IEC 770
Linearity, hysteresis and repeatability as per the limit point method DIN IEC 770? ± 0.05% of the sensor’s nominal measuring range
Activation time< 5s (the device will carry out a self-test.)
Setting time (without damping)< 200ms
Long-time drift? 0.2% of the span per year
Thermal hysteresis? ± 0.2% of the sensor’s nominal measuring range / 10K (-20 to +80°C) from 4bar
? ± 0.3% of the sensor’s nominal measuring range / 10K (-20 to +80°C) up to 0.6bar
Conditions of use
Installation position / calibration positionAny position / standing vertically (position-dependent zero point displacement)
Medium temperatureT1: -40…+125°C (140°C over one hour at the most)
T2: -40…+200°C (high-temperature version)
Ambient storage temperatureType 201/201H:-40…+85°C
Type 200/200H:-30…+75°C
(Below -20°C cable breakage might occur and the display’s function may be impaired.)
Protection class acc. to EN60529IP 67 and IP 69K
Electromagnetic compatibilitySensitivity against interference: acc. to DIN IEC 61000-6-2
Interference radiation:acc. to DIN IEC 61000-6-4