Brainchild Ramp Soak Controllers the Fuzzy Logic plus PID microprocessor-based profiling controller with many segments of the ramp and dwell, incorporate two bright, easy to read 4-digit LED displays, indicating process value and set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance.

As a professional and experienced manufacturer, we supply high-performance and quality ramp soak controllers, which are also called programmable temperature controllers.

Brainchild Ramp Soak Controllers Feature

  • Total 9 profiles, a profile with 16, 32 or 64 segments at most
  • Each segment to be configured as a ramp or dwell(soak)
  • Fast A-D sampling rate (5 times/s)
  • After an event, the process goes to run, hold, abort, manual, failure transfer, off mode, next segment or select the second PID values
  • High accuracy of 18-bit A to D input, and 15-bit D to A output
  • The fast sample rate of 200 msec
  • Fuzzy control to reach set point at the least overshooting and less time
  • Up to three relays are configurable for event output
  • Analog retransmission of process value & setpoint value
  • Optional RS-485 or 232 communications
  • Programmable port for easy configuration or calibration
  • Lockout protection for security requirement
  • Bumpless transfer of safely control while sensor breaks
  • Digital filter to improve the stability of process value
  • SEL function for easy operation

Model

  • P41: 96 x 96 mm
  • P91: 48 x 48 mm

Brainchild Ramp Soak Controllers Specification

power

  • 90 – 250 VAC, 47 – 63 Hz, 12VA, 5W maximum
  • 11 – 26 VAC / VDC, SELV, Limited Energy, 12VA, 5W maximum

Signal Input

Resolution 18 bits
Sampling Rate 5 times / second
Maximum Rating -2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect ±1.5 uV/ °C for all inputs except mA input
±3.0 uV/ °C for mA input
Sensor Lead Resistance Effect T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current 200nA
Common Mode Rejection Ratio ( CMRR ) 120dB
Normal Mode Rejection Ratio ( NMRR ) 55dB
Sensor Break Detection Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 – 5 V input, unavailable for other inputs.
Sensor Break Responding Time Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 – 5 V inputs.

Input

Type Range  Accuracy@ 25 °C Input Impedance
J -120 ~ 1000 °C (-184 ~ 1832 °F) ±2 °C 2.2MΩ
K -200 ~ 1370 °C (-328 ~ 2498°F) ±2 °C 2.2MΩ
T -250 ~ 400°C (-418 ~ 752°F) ±2 °C 2.2MΩ
E -100 ~ 900 °C (-148 ~ 1652 °F) ±2 °C 2.2MΩ
B 0 ~ 1800 °C (32 ~ 3272 °F) ±2 °C (200°C – 1800°C) 2.2MΩ
R 0 ~ 1767.8 °C (32 ~ 3214 °F) ±2 °C 2.2MΩ
S 0 ~ 1767.8 °C (32 ~ 3214 °F) ±2 °C 2.2MΩ
N -250 ~ 1300 °C (-418 ~ 2372 °F) ±2 °C 2.2MΩ
L -200 ~ 900 °C (-328 ~ 1652 °F) ±2 °C 2.2MΩ
PT100 (DIN) -210 ~ 700 °C (-346 ~ 1292 °F) ±0.4°C 1.3KΩ
PT100 (JIS) -200 ~ 600 °C (-328 ~ 1112 °F) ±0.4°C 1.3KΩ
mV -8 ~ 70mV ±0.05% 2.2MΩ
mA -3 ~ 27mA ±0.05% 70.5Ω
V -1.3 ~ 11.5V ±0.05% 650KΩ

Output

Output 1 / Output 2
Relay Rating 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage Source Voltage 5V, current limiting resistance 66Ω .

 

Output
Type Zero Tolerance Span Tolerance Load Capacity
4-20 mA 3.6-4 mA 20-21 mA 500Ω max.
0-20 mA 0 mA 20-21 mA 500Ω max.
0-5 V 0 V 5-5.25 V 10KΩ min.
1-5 V 0.9-1 V 5-5.25 V 10KΩ min.
0-10 V 0 V 10-10.5 V 10KΩ min.

 

Linear Output
Resolution 15 bits
Output Regulation 0.02 % for full load change
Output Settling Time 0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage 1000 VAC
Temperature Effect ±0.01 % of SPAN / °C

 

Triac ( SSR ) Output
Rating 1A / 240 VAC
Inrush Current 20A for a cycle
Min. Load Current 50 mA rms
Max. Off-state Leakage 3 mA rms
Max. On-state Voltage 1.5V rms
Insulation Resistance 1000 Mohms min. at 500 VDC
Dielectric Strength 2500 VAC for 1 minute

 

DC Voltage Supply characteristics(Install at Output2)
Type Tolerance Max. Output Current Ripple Voltage Isolation Barrier
20V ±1V 25mA 0.2Vp-p 500VAC
12V ±0.6V 40mA 0.1Vp-p 500VAC
5V ±0.25V 80mA 0.05Vp-p 500VAC

Alarm

Alarm Relay Form C, Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions Dwell timer,
Deviation High / Low Alarm,
Deviation Band High / Low Alarm
PV High / Low Alarm
Alarm Mode Normal, Latching, Hold, Latching / Hold.
Dwell Timer 0.1 – 4553.6 minutes

Data Communication

Interface RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol Modbus Protocol RTU mode
Address 1 – 247
Baud Rate 2.4 ~ 38.4 Kbits/秒
Parity Bit None, Even or Odd
Stop Bit 1 or 2 bits
Communication Buffer 64 bytes

Analog Retransmission

Output Signal 4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution 15 bits
Accuracy ±0.05 % of span ±0.0025 %/ °C
Load Resistance 0 – 500 ohms ( for current output ),10 K ohm minimum ( for voltage output )
Output Regulation 0.01 % for full load change
Output Settling Time 0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage 1000 VAC min.
Integral Linearity Error ±0.005 % of span
Temperature Effect ±0.0025 % of span/ °C
Saturation Low 0 mA ( or 0V )
Saturation High 22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range 0 – 22.2mA(0-20mA or 4-20mA),
0 – 5.55V ( 0 – 5V, 1 – 5V ),
0 – 11.1 V ( 0 – 10V )

 

User Interface Dual 4-digit LED Displays
Keypad 4 keys
Programming Port For automatic setup, calibration, and testing
Communication Port RS-232 and RS-485

 

Control Mode
Output 1 Reverse ( heating ) or direct ( cooling )action
Output 2 PID cooling control, cooling P band 50 ~ 300% of PB, dead band -36.0 ~ 36.0% of PB
ON-OFF 0.1 – 90.0 ( °F ) hysteresis control ( P band = 0 )
P or PD 0 – 100.0 % offset adjustment
PID Fuzzy logic modified, Proportional band 0.1 ~ 900.0°F,
Integral time 0 – 1000 seconds , Derivative time 0 – 360.0 seconds
Cycle Time 0.1 – 90.0 seconds
Manual Control Heat (MV1) and Cool (MV2)
Auto-tuning Cold start and warm start
Failure Mode Auto-transfer to manual mode while sensor break or A-D converter damage
Ramping Control 0 ~ 900.0°F/minute or 0 ~ 900.0 °F/hour ramp rate

 

Digital Filter
Function First order
Time Constant 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable

 

Profiler
Number of profiles 9
Number of Segment per profile Profile 1,2,3,4 : 16
Profile 5,6,7: 32
Profile 8,9 : 64
Event Outputs 3

Environmental & Physical

Operating Temperature -10°C ~ 50°C
Storage Temperature -40°C ~ 60°C
Humidity 0 to 90 % RH ( non-condensing )
Altitude 2000m maximum
Pollution Degree 2
Insulation Resistance 20 Mohms min. ( at 500 VDC )
Dielectric Strength 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance 10 – 55 Hz, 10 m/s² for 2 hours
Shock Resistance 200 m/s² ( 20 g )
Moldings Flame retardant polycarbonate
Dimensions P41 —96mm(W) X 96mm(H) X 65mm(D), 53 mm depth behind panel
P91 —48mm(W) X 48mm(H) X 116mm(D), 105 mm depth behind panel
Weight P41 — 250 grams
P91 — 150 grams
Approval Standards UL 61010C-1 , CSA C22.2 No. 24-93 ,
EN61010-1 (IEC1010-1)

Protective Class

  • IP65 front panel with an additional option,
  • IP50 front panel without additional option,
  • all indoor use,
  • IP 20 housing and terminals with protective cover.

EMC: EN61326