Firetrol FTA990 Fire Pump Controller: Firetrol FTA990 Disconnecting Devices provide a UL Listed means of disconnecting and isolating the fire pump controller from the incoming power source. The FTA990 gives overcurrent protection coordination upstream of the fire pump controller.

Overcurrent Protection Characteristics of Firetrol FTA990 Fire Pump Controller:
- The protective device shall NOT open for 2 minutes at 600% of the full load current of the fire pump motor(s).
- The protective device shall NOT open with a re-start transient of 24 times the full load current of the fire pump motor(s).
- The protective device shall NOT open within 10 minutes at 300% of the full load current of the fire pump motor(s).
- into for circuit breaker shall NOT be adjustable.
Approvals
UL Listed for fire pump service per:
- NFPA70 (National Electrical Code)
695.4(B)(2)(a)(2) – Normal Power Circuit - NFPA70 (National Electrical Code)
695.4(B)(3)(c) – Markings - NFPA70 (National Electrical Code)
695.3(F)(2) – Alternate Power Circuit - NFPA20 (Standard for the Installation
of Stationary Pumps for Fire Protection)
9.2.3.4.1
Features
The following are included as standard with each controller:
- Suitable for use as service equipment
- NEMA Type 2 (IP22) Enclosure
- Flange-mounted disconnect handle lockable in the “ON” position
Applications
The FTA990 shall be specifically designed to assure complete upstream overcurrent protection coordination with the electric fire pump controller. A flange-mounted disconnect handle lockable in the closed (ON) position shall be standard.
Specifications
disconnecting means shall be a model FTA990, manufactured by Firetrol, Inc. The unit shall be factory assembled and tested. The FTA990 shall be specifically designed to assure complete upstream overcurrent protection coordination with the electric fire pump controller. A flange-mounted disconnect handle lockable in the closed (ON) position shall be standard.
Standards, Listings & Approvals
- Suitable for use as service equipment
- UL Listed for fire pump service per:
- NFPA70 (National Electrical Code) 695.4(B) (2)(a)(2) – Normal Power Circuit
- NFPA70 (National Electrical Code) 695.4(B)(3)(c) – Markings
- NFPA70 (National Electrical Code) 695.3(F)(2) – Alternate Power Circuit
- NFPA20 (Standard for the Installation of Stationary Pumps for Fire Protection) 9.2.3.4.1
Enclosure
The components shall be housed in a NEMA Type 2 (IEC IP22) enclosure.
Overcurrent Protection Characteristics:
- The protective device shall NOT open within 2 minutes at 600% of the full load current of the
fire pump motor(s). - The protective device shall NOT open with a re-start transient of 24 times the full load current
of the fire pump motor(s). - The protective device shall NOT open within 10 minutes at 300% of the full load). for circuit breaker shall NOT be field adjustable.
For More Information and Price: Firetrol FTA990 Fire Pump Controller
Read More Articles:
- Firetrol FTA1300 Electric Fire Pump Controllers
- Firetrol FTA1250 Fire Pump Control
- Firetrol FTA1100J Diesel Engine Fire Pump Controller
- Firetrol FTA1000 Across The Line Starting
- Adalet Hazlo Products and Genlo Product
You must be logged in to post a comment.