J. Schneider AKKUTEC 2402

Overview

J. Schneider AKKUTEC 2402. The battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.
The back-up time is depending from the state of charge of the accumulator and of the discharge current.

The power supply has the following features:

  • Battery charger with I/U-charging characteristics
  • Battery management by micro-controller
  • Battery voltage tracking of the charging voltage by external sensor module (optional)

J. Schneider AKKUTEC 2402  TECHNICAL POST

Nominal input voltage115 … 230 V AC -15% +15%
Nominal frequency47 … 63, Hz
Max. nominal input current0,84 A @ 115 V AC
0,42 A @ 230 V AC
Max. charging current0,25 A
Nominal output voltage24 V DC
Output voltage range (with temp.-sensor)19,8 V DC … 27,8 V DC
Output voltage range (without temp.-sensor)19,8 V DC … 26,8 V DC
Max. nominal output current2 A at 100% ED

Current limit at 1,1 x I Nenn

charge end voltage with temp.-sensor @ 25°27,1 V DC ± 0,4%
charge end voltage without temp.-sensor26,8  V DC ± 0,4%
Efficiency
Battery typePb-Akku, maintenance-free
Buffer timeDepending on battery and load
Degree of protectionIP 20
Operating temperature0 … 45 °C
Storage temperature0 … 50°C
Relative humidity95 % non-condensing
Max. altitude (without derating)2000 a. s. l.
Dimensions (H x W x D)92,5 mm x 60 mm x 116 mm
Weight0,55 kg
FixationSnap-on mounting for DIN top hat rail
Norms and RegulationsEN 50178 / EN 60950

EN 61000-6-4

EN 61000-6-2

UL approvalsUL 508

C22.2

Reference : j-schneider.de