Brainchild R22 Process and temperature controller
Brainchild R22 Process and temperature controller

Brainchild Temperature Transmitter and Controller

Data Communication

ModelC22C62C82C83C72C42R22
InterfaceRS-485
ProtocolModbus RTU (Slave Mode)
Address1 to 247
Baud Rate2.8 KBPS to 115.2 KBPS
Parity BitNone, Even or Odd
Stop Bit1 or 2 Bits
Data Length7 or 8 Bits
Communication Buffer160 Bytes

Analog Retransmission

ModelC22C62C82C83C72C42R22
Output Signal4 – 20 mA, 0 – 20 mA, 0 – 10 VDC
Resolution15 Bits
Accuracy± 0.05 % of Span ± 0.0025% / °C
Load Resistance0 to 500 ? for Current Output, 10 K? minimum for Voltage Output
Output Regulation0.01 % for full load change
Output Setting Time0.1 Second (Stable to 99.9 %)
Isolation Breakdown1,000 VAC minimum
Integral Linearity Error±0.005 % of Span

Analog Retransmission

ModelC22C62C82C83C72C42R22
Temperature Effect±0.0025 % of Span / °C
Saturation Low0 mA or 0 VDC
Saturation High22.2 mAor 5.55 VDC,11.1 VDC minimum
Linear Output Range0 – 22.2mA (0 – 20mA / 4 – 20mA), 0 – 5.55VDC (0 – 5VDC / 1 – 5VDC), 0 – 11.1VDC (0 – 10VDC)

User Interface

ModelC22C62C82C83C72C42R22
Keypad4 Keys
Display Type4 Digit LCD Display
Number of Display232
Upper Display Size0.4”0.58”0.7”0.7”0.58”0.98”0.98”
Lower Display Size0.19”0.3”0.4”0.4”0.32”0.55”0.25”

Programming Port

ModelC22C62C82C83C72C42R22
InterfaceMicro USB
PC Communication FunctionParameter Configuration and Firmware Upgrade

Control Mode

ModelC22C62C82C83C72C42R22
Output 1Reverse (Heating) or Direct (Cooling) Action
Output 2PID cooling control, Cooling P band 50 ~ 300 % of PB, Dead band -36.0 ~ 36.0 % of PB
ON-OFF0.1 °C~50.0 °C( 0.1~ 90.0 °F) hysteresis control (P band = 0)
P or PD0 – 100.0 % off-set adjustment
PIDFuzzy logic modified Proportional band 0.1 °C~500.0°C (0.1~900.0 ), Integral time 0-3,600 Seconds, Derivative time 0-360.0 seconds
Cycle Time0.1 to 90.0 Seconds
Manual ControlHeat (MV1) and Cool (MV2)
Auto-tuningCold Start and Warm Start
Failure ModeAuto transfer to manual mode while sensor breaks or A – D Converter damage
Ramping Control0~500.0 °C (0~900.0°F )/Minute or 0~500.0 °C (0~900.0 °F )/ Hour Ramp Rate