Seametrics FT400 Series Rate & Totalizer Indicator

Description of Seametrics FT400 Series Rate & Totalizer Indicator

Seametrics FT400 Series Rate & Totalizer Indicator
Seametrics FT400 Series Rate & Totalizer Indicator

The FT430/440/450 flow computers are microcontroller-based indicator/transmitters that interface with pulse output flow sensors to compute and display flow rate, and flow total, and also generate output signals representing flow. The FT430 and FT450 have one scaled pulse output and one pulse pass-through. The FT440 has two scaled pulse outputs. The FT450 is battery-powered while the FT430 may be powered by an external DC power source or an optional internal AC power supply*. The FT440 is a “two-wire” or “loop-powered” device, meaning that it is powered by the 4-20 mA loop circuit itself. An optional internal AC power supply* is available for the FT440 with dual 24 and 12VDC outputs to power both the loop and sensors requiring more power than the loop can supply. Pulse and 4-20mA analog outputs can be used to signal external devices, e.g. certain metering pumps and water treatment controls. Alternatively, one or more pulse outputs can be configured as alarm outputs. These flow computers can be password-protected to prevent resetting the total or changing configuration settings. The FT430/440/450 indicators are available in wall and meter mount configurations. The FT430 and FT440 models can also be panel mounted. Order the FT440 only if a 4-20mA output signal is a requirement or the FT450 if internal battery power is needed. Otherwise, the FT430 can be ordered.

Features of Seametrics FT400 Series Rate & Totalizer Indicator

  • Simple Setup
  • DC Powered (FT430)
  • Loop Powered (FT440)
  • Battery Powered (FT450)
  • Remote or Flow Sensor Mounted Indicator
  • Rugged Plastic Housing
  • Non-volatile Memory
  • Data Logging (Optional)
  • Sensus Smart Output (Optional)

Application of Seametrics FT400 Series Rate & Totalizer Indicator

  • Water Treatment
  • Water Utility
  • Industrial Processes
  • Reuse/Reclaim Water
  • Dewatering
  • Irrigation
  • Well Usage Monitoring

Specification of Seametrics FT400 Series Rate & Totalizer Indicator

ModelFT430FT440FT450
Power7-30Vdc, 4mA9-30Vdc, 4mA (4-20 mA when loop-powered)Lithium “C”, 3.6Vdc, replaceable. Life is ~5 years depending on usage.
DisplayRate5-digit auto range
Total8-digit
UnitsRate UnitsGallons/Second/Minute/Hour/Day, Liter/Second/Minute/Hour/Day, Cubic Feet/Second/Minute/Hour/Day, Cubic
Meters/Second/Minute/Hour/Day, Mega Liters/Day, Million Gallons/Day, Fluid Oz/Second/Minute/Hour/Day, Barrels/
Second/Minute/Hour/Day
Total UnitsGallon, Gallon x 1000, Liters, Mega Liter, Cubic Meter, Acre Feet, Cubic Feet, Cubic Feet x 1000, Million Gallon, Acre Inch, Fluid Ounce, Barrels
OutputsPulse Output 1Scaled pulse output, high alarm output or low alarm output. Optoisolated on FT430 and FT440.1
Pulse Output 2Pulse pass-throughScaled pulse output, high alarm output or low alarm output.1Pulse pass-through
Loop Power OutputN/A4-20mA LoopN/A
Set P Range0.1 – 99999.9 units/pulse
Input5V pulse or contact closure5V pulse or contact closureMicropower GMR Sensor (square wave)
Input Range0.752 – 2000Hz
K-Factor Range.001 – 999999.999
Flow Alarm Output Range0.1 – 99999.9
Operating Temperature-5? to 55? C (23? to 131? F)
Non-Operating Temperature-40? to 75? C (-40? to 158? F)
EnvironmentalNEMA 4X, IP67
RegulatoryMark

*Specifications subject to change • Please consult our website for current data
1 Scaled output pulses have a fixed width of 100ms. Maximum pulses per second is 6.5Hz
2 For pulse frequencies <1 Hz, increase the setting in the SET F menu to 3 or higher

PULSE OUTPUT 1 (SCALED)FT430FT440FT450
TYPECurrent sinkingCurrent sinkingCurrent sinking
MAX. VOLTAGE36 Vdc36 Vdc36 Vdc
MAX. CURRENT100 mA100 mA100 mA
MAX. FREQUENCY6.5 Hz6.5 Hz6.5 Hz
PULSE WIDTH100 ms100 ms100 ms
ISOLATION300 V300 VNOTE 1
CONFIGURABLE AS ALARMYES (High or Low)YES (High or Low)YES (High or Low)
PULSE OUTPUT 2 (SCALED)FT430FT440 (Note 2)FT450
TYPENot AvailableCurrent sinkingNot Available
MAX. VOLTAGE36 Vdc
MAX. CURRENT100 mA
MAX. FREQUENCY6.5 Hz
PULSE WIDTH100 ms
ISOLATION300 V
CONFIGURABLE AS ALARMYES (High or Low)
PULSE OUTPUT 2 (PASS-THROUGH)FT430FT440FT450
TYPECurrent sinkingNot AvailableCurrent sinking
MAX. VOLTAGE36 Vdc36 Vdc
MAX. CURRENT10 mA100 mA
MAX. FREQUENCY2000 Hz NOTE 2550 Hz
PULSE WIDTHSAME AS-SENSOR INPUTSAME AS-SENSOR INPUT
ISOLATION300 VNOTE 1
CONFIGURABLE AS ALARMNONO

For More Information and Price: Seametrics FT400 Series Rate & Totalizer Indicator