Aplisens APRE-2000 ALW Smart Differential Pressure Transmitter

Aplisens APRE-2000 ALW Smart Differential Pressure Transmitter is applicable to the measurement of differential pressure of gases, vapours and liquids. The active element is a piezoresistant silicon sensor separated from the medium by separating diaphragms and a specially selected type of manometric fluid.

The special design of the active sensing element ensures that it is able to withstand pressure surges and overloads of up to 250/320/413/700 bar. The casing is made of aluminium alloy cast or 316SS stainles steel, degree of protection IP66/IP67. The design of the casing enables the use of a local display, rotation of the display, rotation of the casing by 0–340° relative to the sensor, and a choice of cable direction.

Aplisens APRE-2000 ALW Metrological Parameters

  • Accuracy:
    • ? ±0,075% of the calibrated range
    • (? ±0,1% for range no. 10)
    • Special version: ? ±0,05% of the calibrated range
    • (? ±0,04% on request)
  • Long term stability (for the nominal measuring range):
    • ? accuracy for 3 years
    • or ? 2 x accuracy for 5 years
    • HS version: ? accuracy for 6 years
    • or ? 2 x accuracy for 10 years
  • Thermal error:
    • < ±0,05% (FSO) / 10°C for ranges no. 1 – 9
    • < ±0,08% (FSO) / 10°C for ranges no. 10
    • max. ±0,25% (FSO) in the whole compensation range
    • spec. version for ranges no 1-9:
      • ? ±0,03% (FSO) / 10°C
      • max. ±0,1% (FSO) in the whole compensation range
  • Thermal compensation range: -25…80°C
  • Zero shift error for static pressure:
    • 0,01% (FSO) / 10 bar for ranges no. 3, 4, 5, 6, 7, 9
    • 0,03% (FSO) / 10 bar for range no. 8
    • 0,06% (FSO) / 10 bar for ranges no. 1, 2
    • 0,01% (FSO) / 10 bar for ranges no. 2, 8 in HS version
    • 0,02% (FSO) / 10 bar for range no. 10
      Zeroing the transmitter in conditions of static pressure can eliminate this error.
  • Response time:
    • 16…480ms (programmable)
    • Exd version: 150ms
  • Additional electronic damping: 0…60 s
  • Error due to supply voltage changes: 0,002% (FSO) / V

Electrical Parameters

  • Power supply:
    • 10…55 VDC / Exia: 10,5…30 VDC / Exd: 10,5…45 VDC
    • SIL2: 15…45 VDC / SIL2 Exia: 16…28 VDC
  • Output signal: 4…20 mA + HART
  • Load resistance (for standard version): R[?] Usup[V] – 10V / 0,0225A
  • Resistance required for communication: min. 240 W

Materials

  • Wetted parts: SS316L, Hastelloy C276
  • Diaphragms: SS316L, Hastelloy C 276, Au
  • Casing
    • Aluminium
    • Option: SS316
    • Material of window: polycarbonate glass, hardened glass

Download Datasheet: Aplisens Smart differential pressure transmitter APRE-2000 ALW

Reference: aplisens.com