Magnetrol E3 Modulevel Liquid Level Transmitter

General Information

Magnetrol E3 Modulevel Liquid Level Transmitter is an advanced, intrinsically safe two-wire instrument utilizing simple buoyancy principle to detect and convert liquid level changes into a stable output signal. The linkage between the level sensing element and output electronics provides a simple mechanical design and construction. The vertical in-line design of the transmitter results in low instrument weight and simplified installation. The instrument comes in a variety of configurations and pressure ratings for varied applications.

Magnetrol E3 Modulevel Liquid Level Transmitter has microprocessor-based electronics with HART® compatible output, in addition to the standard 4-20 mA output. The E3 Modulevel unit supports the FDT/DTM standard and a PACTware™ PC software package allows for additional configuration and trending capabilities.

Magnetrol E3 Displacer transmitter

Magnetrol E3 Modulevel Liquid displacer level transmitter technology operates by detecting changes in buoyancy force caused by liquid level change. These forces act upon the spring supported displacer causing vertical motion of the core within a linear variable differential transformer.

Magnetrol E3 Modulevel ® Liquid Level Displacer Transmitter can be applied in most process or storage vessels, bridles, bypass chambers, interfaces, sumps, and pits up to the unit pressure and temperature ratings. The E3 Modulevel can be used in liquids, clean or dirty, light hydrocarbons to heavy acids (SG=0.23 to 2.20) to meet the safety system requirements of IEC 61508.

magnetrol E3 liquid level transmitter
magnetrol E3 liquid level transmitter

Benefits

  • The E3 Modulevel provides the following benefits to your operation:
  • Suitable for use in environments up to SIL 2 (Safe Failure Fraction = 92.3%) as independently assessed
    (hardware assessment) by exida.com as per IEC 61508/61511-1.
  • Level ranges from 14 to 120+ inches (356 to 3048+ mm).
  • Process temperatures to +850° F (+454° C) for non-steam applications.
  • Process pressures to 5150 psi (355 bar).
  • Continuous self-test with 22 mA or 3.6 mA fault indication fully compliant with NAMUR NE 43.
  • IS, XP, and Non-Incendive approvals.
  • Emission and immunity compliance to EN 61326.
  • Two-wire, loop-powered transmitter for level, interface, or density measurement.

Magnetrol E3 Modulevel Features

  • Two-wire, loop-powered, transmitter for level, interface or density measurement
  • No level change needed for configuration; no field calibration necessary.
  • Safety Integrity Level (SIL) Certified, SFF value of 90.6%
  • 4 –20 mA output signal
  • Two-line, 8-character LCD and 3-button keypad
  • Continuous self-test with 22 mA, 3.6 mA or Hold fault indication fully compliant with NAMUR NE 43
  • Comprehensive diagnostics with faults, warnings & status history
  • HART or FOUNDATION fieldbus digital communications
  • PACTware PC program using HART communication for advanced configuration and troubleshooting (see bulletin 59-101)
  • IS, XP and Non-incendive approvals by FM, CSA, ATEX, IEC
  • Standard output range from 3.8 to 20.5 mA 11 VDC turn on voltage
  • Maximum loop resistance of 620 ohms at 24 VDC
  • Process temperatures to +850 °F (+454 °C) for non-steam applications
  • Level ranges from 14 to 120+ inches (356 to 3048+ mm)
  • Specific gravity as low as 0.23
  • Cast aluminum or stainless steel, TYPE 4X, Cl I Div 1 Groups B, C, D housing
  • Field wiring in isolated junction box
  • Head rotatable through 360°
  • Accepted proven LVDT/range spring technology
  • Range spring suppresses effects of turbulence to produce stable output signal.
    Flanged top mounting or external cage with side/side or side/bottom connections
  • Special options, materials of construction and custom engineered features available (consult factory).
  • Spring protector standard
  • Signal sampling 15 times per second

Applications

  • MEDIA: Liquids or slurries, clean or dirty, light hydrocarbons to heavy acids (SG=0.23 to 2.20)
  • VESSELS: Process & storage, bridles, bypass chambers, interface, sumps & pits up to unit pressure & temperature ratings.
  • CONDITIONS: Most liquid level measurement and control applications including those with varying dielectric, vapors, turbulence, foam, buildup, bubbling or boiling and high fill/empty rates. Also, liquid/liquid interface level measurement or density control.

Operating Principle

Changing buoyancy forces caused by liquid level change act upon the spring-supported displacer causing vertical motion of the core within a linear variable differential transformer.

As the core position changes with liquid level, voltages are induced across the secondary windings of the LVDT. These signals are processed in the electronic circuitry and used to control the current in the 4-20 mA current loop. The enclosing tube acts as a static isolation barrier between the LVDT and the process media.

Specifications

  • System Design : Measurement Principle Buoyancy – continuous displacement utilizing a precision range spring
  • Input
    • Measured Variable Level, determined by LVDT core movement affected by buoyancy force changes on continuous displacer
    • Physical Range Up to 120″ (300 cm) based on displacer length (consult factory for longer ranges)
  • Output
    • Type
      • 4 to 20 mA with HART Version 6.x
      • 3.8 to 20.5 mA useable (meets NAMUR NE 43)
      • FOUNDATION fieldbus, H1 (31.25 kbits ?sec), Available blocks AI, PID, RB, TB
      • LAS capable, ITK 5.0 interoperability tested
    • Resolution Analog: 0.01 mA, Display: 0.1%, Level Units: 0.01 inch
    • Loop Resistance (maximum) 620 ohms @ 24 VDC
    • Diagnostic Alarm 3.6, 22 mA or HOLD selectable (meets NAMUR NE 43)
    • Damping Adjustable 0-45 seconds
    • Sampling Rate Transmitter 15 times per second
  • User Interface
    • Keypad 3-button menu-driven data entry and system security
    • Indication 2-line × 8-character LCD display
  • Power
    • Measured at instrument terminals 11 to 36 VDC HART, 9 to 32 VDC FOUNDATION fieldbus (Direct
    • Current) This device provides only Functional Isolation.
    • Current 22.5 mA maximum HART, 17 mA (maximum current draw) FOUNDATION fieldbus, This device provides only Functional Isolation.
  • Housing
    • Material Aluminum A356-T6 (<0.20% copper), optional 316 stainless steel
    • Cable Entry 3
    • ?4″ NPT and M20
    • Ingress Protection TYPE 4X, IP66
  • Chamber
    • Materials Carbon steel and 316/316L stainless steel
    • Wetted parts 316/316L and Inconel ® (spring)
    • Process connections
      • Tank Top: 3″, 4″, 6″ ANSI Flange
      • Chambered: 11 ?2″, 2″ NPT, Socketweld, ANSI Flanges
  • Process Conditions
    • Process temperature range ¿
      • Steam applications: -20 to +800 °F (-29 to +427 °C)
      • Non-steam applications: -20 to +850 °F (-29 to +454 °C) ¡
    • Process pressure range 5150 psig @ +100 °F (355 bar @ +38 °C)
  • Environment
    • Electronics Operating Temperature -40 to +176 °F (-40 to +80 °C)
    • Display Function Operating Temperature -5 to +160 °F (-20 to +70 °C)
    • Storage Temperature -50 to +185 °F (-40 to +85 °C)
    • Humidity 0-99%, non-condensing
    • Electromagnetic Compatibility Meets CE Requirement: EN 61326
    • Surge Protection Meets CE Requirements EN 61326
    • Shock Class ANSI/ISA-S71.03 Class SA1 ¬
    • Vibration Class ANSI/ISA-S71.03 Class VC2 ¬
    • Altitude ?2000 m
    • Pollution Degree 2

Download Datasheet: Magnetrol E3 Modulevel® Liquid Level Transmitter