Description
Eska ERG-H1 Gas pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure. ERG-H1 series pressure regulators are suitable for commercial usage like Gas Skids where the maximum inlet pressure up to 20 bar and outlet pressure up to 4bar. It is mainly used in Distribution of Natural Gas and also suitable to use with non-corrosive gases.
ERG-H1 is a single stage regulator with an optional security systems such as relief valve, UPSO and OPSO. The regulators are manufactured according to Ped Directive 2014/68/EU. The performance of the regulators complies with EN 334.
Relief System
Regulator can be produced with a relief valve. Relief valve monitors outlet pressure continuously and when it detects pressure level higher than regulator’s nominal outlet pressure, it activates and discharges gas to the atmosphere. Relief valve has limited discharge capacity. Usually calibration point is lower than OPSO system. Under certain conditions such as gas expansion during hot weather seasons, Relief Valve is activated before OPSO closes the gas lines. It prevents random shut-off regarding pressure increase on outlet side. Relief valve can be recalibrated by using proper tools.
Over Pressure Shut-Off System
OPSO system is very useful during major breakdown situations and keeps the customer side safe. System works as a security valve and activates itself when the outlet pressure passes OPSO calibration point. OPSO system cuts the gas off, and manual reset is needed to activate the regulator again. System has an independent shut-off mechanism and orifice and it monitors outlet pressure changes continuously, so activation time is below 2 seconds.
Eska ERG-H1 Gas Pressure Regulator Features
- For medium and high pressure domestic or industrial second group gas lines.
- Max inlet pressure 1 to 20 bar.
- Max outlet pressure MPO: 100 to 800 and HPO : 800 to 4 bar.
- Optional filter on inlet.
- Outlet pressure tolerance is ±%5-10 (AC5&AC10)
- Lock up pressure tolerance is max +%30 (SG30)
- Can be integrated with Relief valve & UPSO & OPSO
- Flow direction inline and angle type.
Specification
Medium | Natural Gas, LPG and Non-Corrosive Gases |
Operating Temperature | -20… + 60°C (optional : -40… +60°C) |
Assembly | Vertical and Horizontal Position |
Maximum Inlet Pressure | 6 bar (Optional 10 bar, 20 bar) |
Outlet Pressure Range | 100 mbar to 4 bar. |
Conforming | 2014/68/EU |
Filter | As a standard 100 micron pore diameter |
Download data Sheet: ERG-H1 Direct Acting Gas Pressure Regulator
Ref: en.eskavalve.com
Other Article:
- LEEG Pressure Transmitter, Sensor and Switch
- D22 Pressure Transmitter Delta Mobrey
- 8000 SAN Pressure Transmitter Delta Mobrey
- Hengesbach Pressure Transmitter DME 11 Series
- Pressure Transmitter 8000 Series Delta Mobrey