General Information
The Fluidwell F127 flow computer has been developed to calculate corrected differential liquid volume at normal conditions. This is calculated by measuring the uncorrected volumetric flow and actual line temperature in both the supply and return lines. These signals are processed with the thermal expansion coefficient algorithm stored in the flow computer.
The reference temperature can be defined as desired (e.g. 15°C, 20°C, or 60°F). The usual difficulties encountered in such applications include: pulsating flows, very low consumption readings, vibration, and high ambient temperatures. These are all well-catered for in the design and operation of the F127.
The display shows the compensated consumption/flow rate, total, accumulated total, and actual line temperatures. On-screen engineering units like Nm³ are easily configured from a comprehensive selection.
Advantages
- Robust aluminum or stainless steel 316L field enclosure (IP66, IP67 / NEMA Type4X).
It is so rugged, that a truck can even stand on it! - Intrinsically Safe available – ATEX and IECEx approval for gas and dust applications.
- Familiar easy operation with the Fluidwell “Know one, know them all” configuration structure, saving time, cost, and aggravation.
- Very diverse mounting possibilities: walls, pipes, panels, or directly onto outdoor sensors.
Features
- Displays corrected consumption (flow rate), total, and accumulated total.
- Supply line: displays actual temperature and corrected flow rate.
- Return line: displays actual temperature and corrected flow rate.
- Analog output signal reflecting the corrected consumption/flow rate.
- Displays total and flow rate simultaneously.
- Large digit selection for flow rate or total.
- Flow rate: seven 17mm (0.67″) or 8mm (0.31″) digits.
- Total – resettable: seven 17mm (0.67″) digits.
- Accumulated total – not resettable: eleven 8mm (0.31″) digits.
- Temperature: six 17mm (0.67″) digits.
- Engineering units for flow rate, total, and temperature on the display.
- LED backlight.
- Intrinsically safe according to ATEX and IECEx.
- GRP, Aluminum, or high-grade stainless steel enclosure.
- Auto backup of settings and running totals in EEPROM memory.
- Ambient temperature: -40°C to +80°C (-40°F to 176°F).
- Various accessories are available for this product.
Applications

- Net fuel consumption calculation for diesel engines on board ships or locomotives, generators, or burners, corrected for the influence of thermal product expansion.
- The F-Series is your first and best choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, sandy deserts, salty atmospheres, and temperatures between -40°C up to +80°C (-40°F up to 176°F).
Product specifications
Signal Inputs
- Flowmeter Inputs
- Pulse type inputs: Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal.
Different pulse signal types are allowed for inputs A and B.
- Pulse type inputs: Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal.
- Temperature Inputs
- PT100 – 2 or 3-wire PRTD sensor.
- (0)4 – 20mA.
Signal Outputs
- Pulse outputs
- Function: One scaled pulse output according to differential or sum accumulated total (e.g. a pulse every 3.25 gallons) and one configurable pulse, negative or decreasing total output.
Max. frequency: 500Hz.
Adjustable pulse length from 0.001 sec. to 9.999 seconds. - Type: Two passive NPN transistors, active PNP transistors or isolated electro-mechanical relays.
- Function: One scaled pulse output according to differential or sum accumulated total (e.g. a pulse every 3.25 gallons) and one configurable pulse, negative or decreasing total output.
- Alarm outputs
- None
- Analog outputs
- Function: Re-transmitting the compensated differential flow rate (consumption) – the output can be scaled to any range (e.g. 200 L/min to 1200 L/min).
- Type: One passive isolated, floating or loop powered 4 – 20mA output or one active (0)4 – 20mA or 0 – 10V DC output.
Supply
- Power Supply
- Long-life Lithium battery.
- 4 – 20mA Output loop-powered.
- 8 – 24V AC/DC.
- 115 – 230V AC.
- Basic: 8 – 30V DC.
- Sensor Supply
- 3.2, 8.2, 12, 24V DC.
Hazardous Area
- Intrinsically Safe
- ATEX:
Gas: II 1 G Ex ia IIB/IIC T4 Ga
Dust: II 1 D Ex ia IIIC T100 °C Da - IECEx:
Gas: Ex ia IIC/IIB T4 Ga
Dust: Ex ia IIIC T100 °C Da
- ATEX:
- Explosion Proof
- ATEX:
Gas: II 2 G / Ex d IIB T5 Gb
Dust: II 2 D / Ex t IIIB T100°C Db
- ATEX:
Communication
- Function: All process data and settings can be read and modified through the communication link.
Download Datasheet: Fluidwell F127 Flow Computer
For information Price, stock and other please contact: WMA
Other Article:
- Fluidwell F490 Loop Powered Multi-Purpose Indicator
- Fluidwell F133 Intrinsically Safe Delivery Controller / Dispenser
- Fluidwell F130 Batch Flow Control
- Fluidwell F Series Flow Display and Level Control
- Fluidwell F119 Flow rate Indicator with receipt printer driver
- Fluidwell Display, Indicator, Totalizer, and Batch Control for Flow and Level
- Fluidwell F Series Flow Display and Level Control
- Cartridge Fuse General Duty Safety Switch
- Fluidwell Display, Indicator, Totalizer, and Batch Control for Flow and Level Meter
- Fluidwell B Series Basic Flow Indicator
- Fluidwell D Series DIN Panel Mount Flow Indicator
- Battery Powered Flow Rate Transmitter RT-10 Series AW Lake
- KEPmeter ST1-MANIFOLD-FC-2 Channel Manifold Controller
- Hengesbach Level Module NC1 Series
- Fluidwell E Series Explosion Proof
- Fluidwell N Series Batch Controller
- Flow Computer, Batch Control, Flow Indicator, and Level Indicator Fluidwell
You must be logged in to post a comment.