Kimo Fluxicont FU4SK / FU4LK Process and Automation Instruments

About Kimo Fluxicont FU4SK / FU4LK Process and Automation Instruments

Flow transmitter/flow switch for general industrial and for hygienic and aseptic applications. The device is an electronic flow resp. temperature switch for monitoring, control, and continuous measurement of flow and temperatures in liquids. A high variety of versions of process connections and electronic types allows the use for a wide range of applications, also for demanding measuring requirements.

The process connection of the FU4LK with metallic sealing has been specifically designed for hygienic, dead-space, and elastomer-free process adaption. Due to its high accuracy and the digital adjustability by RS485 Modbus®-RTU or IO-Link®, the device can be suited to a wide variety of applications.

The robust design and the high-quality workmanship turn the device into a very high-quality product, which even the most adverse environmental conditions cannot affect, whether the lowest temperatures when used outdoors, extreme shock and vibration stress or aggressive media.

A captive laser marking of the type label ensures identifiability throughout the entire lifetime of the device. Is the optional marking of a measurement point designation resp. TAG, a customer label or of a neutral type label, of course also per laser marking.

A LABS- resp. silicone-free version, a factory calibration with calibration certificate, and a customer-specific configuration resp. preset is also optionally available like a material test certificate EN10204 3.1 or a factory certification for drink water resp. food suitability. Customer-specific special versions can be realized short-term on request, e.g. special designs for the process connection or other process materials.

Kimo Fluxicont FU4SK FU4LK Process and Automation Instruments
Kimo Fluxicont FU4SK FU4LK Process and Automation Instruments

Advantages

  • Flow velocities from 3cm/s to 300cm/s
  • Wide variety of process connections and sensor lengths
  • Wear-free calorimetric sensor
  • Process temperature range –20°C to +110°C
  • FU4LK: Useable for CIP/SIP cleaning
  • FU4LK: Elastomer-free and free of dead space metallic sealing connection
  • High process pressure tightness up to 40bar
  • Fully welded robust steel enclosure
  • High protection class IP69K/IP67
  • Evaluation electronic RS485 Modbus®-RTU / IO-Link

Application

FU4SK is suitable for general applications in

  • Machinery and plant engineering
  • Air-conditioning and refrigeration plant engineering
  • Hydraulic and pneumatic systems
  • Process industry
  • Environmental technology

FU4LK is suitable for general applications in

  • Food and beverage industry
  • Pharmaceutical industry
  • Biotechnology
  • Sterile process engineering

Technical data

  • Measuring range
  • Measuring principle Calorimetric flow measurement
  • Nominal measuring range 3…300 cm/s
  • Output type V – RS485 Modbus®-RTU
  • Interface RS485, bidirectional / Modbus®-RTU / 9600 Baud (4800…38400 Baud)
  • Time behavior Flow: T90 ? 6s / ton ? 10s
  • Temperature: T90 ? 4s / ton ? 2s
  • Output type L – IO-Link®
  • Interface IO-Link® V1.1 / Com2 (38400 Baud)
  • Analogue output 0…20mA: 0…20,5mA / ? 0,05mA / ? 22mA / dI ? 1µA 4…20mA: 3,8…20,5mA / ? 3,6mA / ? 22mA / dI ? 1µA
  • Switch output 2x PP (Push-Pull), switch to +L/-L
  • Output Uout ? 0,2V, ? Us – 2V / Iout 0…200mA (current limited ? 450mA, short circuit protected)
  • Time behavior Flow: T90 ? 6s / ton ? 10s
  • Temperature: T90 ? 4s / ton ? 2s
  • Auxiliary power Supply voltage Us polarity protected Type V – RS485 Modbus®-RTU: 6…35VDC Type L – IO-Link®: 9…35VDC, without IO-Link® / 18…30VDC, with IO-Link®
  • Measuring accuracy Accuracy Flow: ? ±5% Measuring end value (5…100cm/s) / (-20°C…+85°C) / ? ±10% Measuring end value (100…175cm/s) / (-20°C…+85°C) Temperature: ? ±1,5K (? 20cm/s)
  • Long term drift Flow: ? ±10% of measuring value / year (-20°C…+85°C)
  • Temperature deviation Flow: ? ±0,4cm/s / K (-20°C…+85°C)
  • Process conditions
  • Process temperature -20°C…+110°C, +140°C/1h
  • Process pressure ? 40 bar
  • Environmental conditions
  • Environmental temperature -20°C…+100°C
  • Protection level IP69K/IP67 (EN/IEC 60529)