J. Schneider AC C-TEC 1203-1 Capacity buffered Power Supply. The buffered DC power supply of the AC C-TEC series includes ultra-capacitors as energy storage inside the housing. During normal operation this capacitor is charged from AC-mains. The connected DC consumers are supplied as well from AC mains. In case of an interruption of the AC supply, the energy of the ultra-capacitor is realesed regulated. With a dc/dc converter the load is supplied from the capacitor until it is discharged. The backup time depends on the state of charge of the capacitor and the discharge current.
The power supply hast he following characteristics:
- Maintenance-free because of long-life ultra-capacitors
- Mikrocontroller based charging and discharging of the ultra-capacitors
- Control of operation and status of charge with potential-free contacts and LED
- Capacity extension possible with external capacitor extension modules
J. Schneider AC C-TEC 1203-1 Technical Data
Nominal input voltage | 115 … 230 V AC ±15% |
Min. nominal Input voltage for charging operation | 97,8 V … 264,5 V AC |
Nominal frequency | 47 … 63 Hz |
Max. nominal input current | 0,84 A … 115 V AC |
0,42 A … 230 V AC | |
Max. inrush current | 30 A / 2 ms |
nominal Output current max. | 3 A DC (at 0,94 kJ) |
nominal Output current at max. energy | 2 A DC (at 1 kJ) |
Current limitation | 1,05 … 1,5 x INenn |
Nominal Output voltage (in mains operation) | 12,3 V DC ± 2 % |
Output voltage range (in back-up operation) | 11,5 V DC ± 2 % |
efficiency | 88 % @ (Ue=230Â VÂ AC; Ua=24,3Â VÂ DC; Ia=INenn) |
Energy | 1 kJ |
Protective system | IP20 a. EN 60529 |
operational temperature | -40 … 60 °C |
storage temperature | -40 … 60 °C |
Relative humidity | 95 % condensation not permissible |
Max. mounting height without load reduction | 2000 m above sea level |
Dimensions (H x W x D) | 152,5 mm x 72 mm x 130mm |
weight | 0,85 kg |
Fixation | Snap-on mounting for DIN top hat rail |
or mounting bracket for mounting plate | |
Norms and regulations | EN 50178 |
EN 60950 | |
UL approval | UL 508 |
C22.2 |