Description
AW-Lake FIP Analog Output Sensor is a microprocessor based, meter mounted, analog output sensor. Each unit has a sensor, amplifier and converter module built into an aluminum junction box. The FIP is designed to handle frequencies up to 5,000 Hz. The operational frequency range is user defined via four BCD rotary switches, where the high flow rate in frequency is set to 20 mA, 5V or 10V, and the output signal is automatically scaled. Electrical connection options include ½” NPT for running conduit piping, 4-pin connector or 3-pin connector. For use with all JV-CG and JV-KG gear meters
AW-Lake FIP Analog Output Sensor Features:
- Meter Compatibility: Used with all JV-CG and JV-KG meter
- Sensor Type: Current or voltage signal output sensor
- Conversion: Converts frequency to an analog output (includes sensor)
- Available in six outputs: 1-5 VDC, 2-10 VDC, 4-20 mA, 0-5 VDC, 0-10 VDC, and 0-20 mA
AW-Lake FIP Analog Output Sensor Specification:
- Supply Voltage: 10-30 VDC
- Supply Current: 60 mA max
- Signal Output:
- 0-20 mA, 4-20mA or
- 0-5V, 0-10V, 1-5V, 2-10V
- Max Load Impedance: (Vcc/0.02) – 275 ohm (for mA out)
- Min Load Impedance: 500 ohm (for Volt out)
- Driving Capacity: For Voltage output only 10 mA max
- Temperature Range: 0-185° F
- Jumper Settings
- J1 AB:
- Analog Output
- BC:
- Frequency Output
- J2 AB:
- Housing Ground
- CB:
- Signal ground
- Response Time:
- 1/F + 25 msec
- Frequency Input:
- 5 KHz max
- Diagnostics:
- A glowing LED indicates the unit is working.
- The LED will blink to show an active frequency.
Download Data Sheet: Analog output sensor FIP
Ref: aw-lake.com