AW-Lake Flowstat ES Paddle Wheel Flow Meter

Description

AW-Lake Flowstat ES Paddle Wheel Flow Meter is ideal for monitoring various fluids in applications such as chillers/cooling circuits, HVAC, batching, and industrial process control applications.

The FlowStat flow rate meters integrates rugged tangential turbine technology with a precision digital to analog conversion circuit hermetically encapsulated within the body of the meter. The flow meter is ideal for measuring flow rates in cooling circuits, HVAC systems and batching operations.

AW-Lake Flowstat ES Paddle Wheel Flow Meter Features:

  • Measuring Accuracy: ±2.0% of full scale
  • Flow Ranges: 0.5-15 GPM (2-60 LPM)
  • Pressure Rating: up to 150 PSI
  • Temperature Rating: 20-150°F

Advantages:

  • Value Pricing: Low cost operation combined with low cost maintenance, equals better bottom line savings form your operation.
  • Encapsulated Circuitry: Withstands the harshest environments.
  • Several Outputs Available: The standard interface is a 2-wire, 4-20mA current loop. Sensor signal may be transmitted on a low cost wire without degradation. Pulse, relay and 0-5 VDC (regulated) are also available.
  • Connects Directly to your Flow Monitoring Instruments: Can be connected directly to analog acquisition cards, chart recorders or other monitoring instruments, without external signal conditioning.
  • Simply Plumb and Apply Power: Comes factory calibrated to your flow range specifications.

AW-Lake Flowstat ES Paddle Wheel Specification:

  • Measuring Accuracy: 2% of full-scale
  • Repeatability: ±0.5% of full-scale
  • Flow Measuring Range: 0.5-15 GPM (2-60 LPM)
  • With optional low-flow adapter: 25-4.5 GPM (1-17 LPM)
  • Turn Down Ratio: 10:1
  • Maximum Operating Pressure: 150 PSIG
  • Maximum Operating Temperature: 20-150°F
  • Standard Calibration Fluid
    • Tap water @ 70°F Temperature (21°C), 1.0 sg
  • Filtration Requirement: 150 Micron Filter recommended

Material Construction

Wetted Components
ComponentMaterials
CasingGlass-Filled Polypropylene
CoverClear Polycarbonate
SealBuna-N® (Other options available)
ImpellerAcetal Copolymer
BearingPEEK (Polyetheretherketone)
ShaftStainless Steel
Non-Wetted Components
ComponentMaterials
EncapsulantEpoxy
Strain ReliefNylon
Lock RingGlass-Filled
Polypropylene
Wire InsulationHigh-Temperature
PVC

ELECTRONIC SPECIFICATIONS

4-20 mA version

  • Power Requirements 12-24 VDC, Regulated, Loop powered
  • Load driving capacity Use the following equation to calculate maximum load resistance: Max Loop Load (?) = 50 (Power supply volts – 12).
  • Maximum Transmission Distance Limited only by wire resistance & supply voltage
  • Response time 2 seconds to 90% (step change)
  • Resolution Infinite
  • Over-current limit Self limiting at 35 mA
  • Other protection Reverse polarity

0-5 VDC (regulated) version

  • Power Requirements 12-24 VDC, Regulated
  • Maximum Current 25 mA DC, Regulated
  • Minimum Load resistance 1000 Ohms
  • Maximum Transmission Distance 200 feet recommended
  • Resolution Infinite
  • Response time < 5 seconds to 90% (step chang

Relay Output

  • Power Requirements 12-24 VDC, Regulated
  • Maximum Transmission Distance 200 feet recommended
  • Switch Contact Form C, 5A max 120 or 240 VAC
  • Set Point Repeatability 1% of full scale

Pulse Output Version

  • Power Requirements 12-24 VDC, Regulated
  • Response Time <100 mS
  • Maximum Current 25 mA DC, Regulated
  • Maximum Transmission Distance : 200 feet recommended
  • Minimum Load Resistance 1000 Ohms
  • Protection Short circuit & reverse p

PART NUMBER GUIDE

AW-Lake Flowstat ES part number guide
AW-Lake Flowstat ES part number guide

Download Data Sheet: AW-Lake Flowstat ES

Ref: aw-lake.com