Delta-Elektrogas CFK Burner Control System is an advanced, microprocessor-based management unit designed to automate and monitor the ignition and flame supervision of atmospheric or fan-assisted gas burners. Engineered to comply with the rigorous safety standards of EN 298, the CFK series provides a comprehensive “all-in-one” solution for sequence control, managing critical phases from pre-purge and spark ignition to continuous flame monitoring via ionization or UV sensors. By integrating failsafe logic and diagnostic status indicators into a compact, plug-in design, the CFK system ensures maximum operational safety and minimized downtime for industrial thermal processing equipment, including boilers, ovens, and space heaters.

Technical Specification Of Delta-Elektrogas CFK Burner Control System
| Feature | Specification Details |
| Safety Standard | Compliant with EN 298 (European Standard for Burner Control) |
| Supply Voltage | 230V AC or 115V AC (+10% / -15%); 50/60 Hz |
| Power Consumption | Approx. 3 VA |
| Flame Detection | Ionization Probe or UV Sensor (e.g., Elektrogas UV1/2) |
| Ionization Current | Minimum 1.5 µA (Stable operation requires > 5 µA) |
| Pre-Purge Time ($t_1$) | Typically 30 seconds (Standard) |
| Safety Time ($t_s$) | 3, 5, or 10 seconds (Factory set/Model dependent) |
| Switching Output | Max 2A per output (Gas valve, Fan, Ignition) |
| Operating Temp | -20°C to +60°C |
| Ingress Protection | IP40 (Standard) |
Features Of Delta-Elektrogas CFK Burner Control System
- Automated Sequence Control: Manages the entire burner lifecycle, including pre-purge (cleaning the combustion chamber), ignition timing, and safety intervals to prevent gas buildup.
- Dual Flame Supervision: Offers flexible monitoring using either an Ionization Probe (flame rectification) or a UV Sensor, providing a failsafe lockout if the flame is not detected or is lost during operation.
- Integrated Ignition Transformer: Certain models feature a built-in high-voltage ignition system, which simplifies installation by reducing external wiring and the number of components in the gas train.
- Airflow Verification: Includes a dedicated input for an Air Pressure Switch, ensuring the combustion fan is functional and providing sufficient oxygen before the gas valves are permitted to open.
- Visual Diagnostics & Reset: Equipped with a multi-color LED button that communicates the system status (Operation, Standby, or Lockout) and allows for both local and remote resetting of the controller.