The ARC900 Series Paperless Recorder features the most advanced technology. It can be applied across a broad scope of industrial applications. ARC900 is the product which with multi-channels, complete functions, easy operation, high accuracy, low power but high performance. And the series overcome the old-fashioned paperless recorder, which has less channels, multiple installation and space-consuming problem.
ARC 900 Paperless Recorder used the most advanced technology, to be aimed at various industry applications. ARC900 is a product that with multi-channels, complete functions, easy operation, high accuracy, low power but high performance. And the series overcomes the old-fashioned paperless recorder, which has fewer channels, multiple installations and space-consuming problems.
Paperless Recorder | ARC 900 Recorder | Alia Recorder
ARC 900 Paperless Recorder Features
- DIN Size(144mm*144mm), 320*240Pixels,TFT truecolor(LCD).
- 128MB memory installed inside, applied to long terms data record.
- Common input signal, mA, Include VDC, T/C, RTD,Hz..etc
- High Accuracy +/-0.15% of Reading.
- Maximum to 12 points Relay, 4 point 4-20mA output and 24VDC output.
- Maximum can receive 16 channels input signal.
- Could selected 24VDC Aux. Power supply for 2 wires system.
- It can Display/Record single point,Multi-point,Trend,Totalizer,Bargraph.
- The recorded data could be stored in USB memory & SD memory card and take out to computer make soft analysis.
Specifications
| Number of Inputs: | Display: |
| 1-16 Channels | 5.6″ color-screen LCD |
| Inputs: | Trend & Bargraph |
| T/C (K, S, B, E, J, N, T, R,N, etc.) | Vertical / Horizontal / Landscape |
| RTD,CU50, CU53,BA1, BA2 | Digital |
| DCA(4-20 mA, 0-10 mA, 0-20 mA) | 4-1/2 digits programmable |
| DCV( 0-5V, 1-5V ,0-10V, 20mV, 100mV) | Engineer unit |
| Frequency(1Hz ~ 5KHz) | 66 Engineering units |
| Resistance(0-175 , 0-400 ) | Parameter Protect |
| Accuracy: | Password entry(6 Digits) |
| +/-0.15% of Span | Logging Rate: |
| Response Time: | 1 Seconds ~ 1800 Seconds Per Pen |
| 50 ms | Recording Capability: |
| Alarm Types: | 120 Hours(16 Points, 1 Data/Second) |
| High & Low alarm, Incr. & Decr. alarm | 18936 Years(1 Point, 1 Data/Hour) |
| Output: | PC software: |
| 4-20 mA *4 points Maximum, Load:800 | Compatible with Windows 2000/XP/Vista |
| Relay, 3A/250V * 12 points Maximum | Display |
| 24VDC, 65 mA *4 points Maximum | Trend, Digital, Circular, Alarm, Bargraph |
| Digit Input: | Totalizer |
| 2 Points Maximum | Convert function |
| Storage Memory: | Can be save as excel files |
| 128 MB(on board) | Enclosure: |
| Recycling Mode: | NEMA 3 / IP 54 |
| Newest Data over-writes to oldest data | Weight: |
| Recording Data Shift: | 2.6 Kg maximum |
| USB memory(8GB) / SD Card(4GB) | Dimensions: |
| Display update Rate: | 144 mm (W) * 144 mm (H) * 219 mm (D) |
| 1 Second | Ambient Temperature: |
| Keyboard: | -10 to +60 oC |
| 6 Keys (Page,Left,Right,Up,Down,Enter) | Ambient Humidity: |
| for programming and display control | 10% to 85%RH (at 5 to 40 oC ) |
| Parameter Storage: | Power Supply: |
| Operation Parameters are stored by | 85-260VAC, 50/60Hz |
| EEPROM for more then 10 years | Vibration Test: |
| 10~60Hz ,10m/S2 for 3 hours | |
| Power Consumption: | |
| <=20 W | |
| Communication: | |
| RS232 / RS485 (MODBUS Protocol) |