Bamo CF30 Level Float Switch for Retention Receiver, the float lift up a stem actuating a change-over contact. The fitting allows installation on almost any day-tank or retention receiver. The stem length may be modified on request. Several versions are available depending on detection heights and mounting:
CF30 Model:
The float is mounted vertically to reduce dimensions. Distance H: Min. 150 mm Distance H: Max. 950 mm Detection from 100 mm of liquid as a minimum (depending of H).
CF31 Model:
The float is mounted horizontally for a detection as soon as possible. Distance H: Min. 150 mm Distance H: Max. 2000 mm Detection from 20 mm of liquid as a minimum (depending of H).
CF32 Model:
Similar to CF30, but with BSP 2” fitting
Bamo CF30 Features
- For retention receiver and gutter
- Stem length: from 150 to 2000 mm
- Easy installation
- Output: contact, potential free
- Head housing: IP 54
Application
The float switch CF30 and its variants, are designed to detect a leak from the main tank falling into the retention receiver. Compatibility with liquids (examples):
- Diesel
- Lubricating oil
- Rainwater
- Water-glycol mixture
As it is a simple controller, much more applications are available.
Bamo CF30 Specification
Materials | Stem: Stainless steel |
Float: Foamed PVC | |
Head housing | IP 54 |
Operating pressure | Atmospheric |
Operating temperature | Between 0 and 40 °C |
Contact(s) | 1 changeover contact, 4 A, 230 V, potential-free |
Factory setting |