Dinel CLM–36 Capacitive level meters are designed for continuous level measurement of liquids, powders, and bulk-solid materials in vessels, tanks, sumps, containers, silos, etc. CLM consists of a stainless steel housing with an electronic module and the measuring electrode. The electronic part converts the capacity into the current signal (4 … 20 mA) or voltage signal (0 … 10 V). Sensitivity (SPAN) and initial capacity compensation (ZERO) can be fluently set.
Level meters are produced in the following performances: N – for non-explosive areas, NT – high temperature for non-explosive areas, Xi – Explosion-proof – intrinsically safe for hazardous (explosive) areas, and XiT – high-temperature conf. for explosive environments. CLM is offered in variants with various types of process connections (thread, Tri-clamp).
Dinel CLM–36 For continuous level measurement of liquid and bulk solid materials
- Direct mounting into containers, silos, basins, vessels, reservoirs, etc.
- Easy and quick connecting by a connector
- Continuous adjustment of initial capacity
- Current (4 … 20 mA) or voltage (0 … 10 V) output
- Removable electronic module
- The material of housing and rod electrodes from stainless steel
- Xi, XiT versions for usage in explosive areas
Dinel CLM–36 Technical Data
Supply voltage | CLM – 36N(T)–_ _–_–I | 9 … 36 V DC |
CLM – 36N(T)–_ _–_–U | 16 … 36 V DC | |
Current output | 4 … 20 mA | |
Voltage output | 0 … 10 V * | |
Power consumption (off-load) CLM–36N(T)–_ _–_–U | approx. 8mA | |
Sensitivity ranges | 20; 30; 50; 100; 150; 300; 500; 1000 pF | |
Initial capacity regulation ratio | min. 1:2 | |
Nonlinearity | max. 1 % | |
Temperature error | max. 0,05% / K | |
Voltage error for current and voltage output | max. 0,3 ?A/V and 0,1 mV/V | |
Internal resistance / Electric strength (Electrode – Housing) | 1 M? / 250 V AC | |
Coupling capacity / Electric strength (Housing – Supply leads) | 51 nF / 250 V AC | |
Protection class | ||
standard | IP67 (Housing), IP65 (Connector) IP67 | |
Optional (Connector GAN-DADE 7A / DAEE 7A) | ||
Maximal load (serial) resistance for current output (U = 24 V) | Rmax= 750 ? | |
Minimal load resistance for voltage output | Rmin > 1 k? | |
Maximum tensile strength of the rope electrode | 1400 kg | |
Recommended cable | PVC 2×0,75 mm2 (3×0,5 mm2) | |
Weight (exclude electrode) | ||
Version N, Xi | approx. 0,5 kg | |
Version NT, XiT | approx. 1 kg |