Dinel IRU–420 Isolating Repeater Level Controller
Dinel IRU–420 Isolating Repeater Level Controller

Dinel IRU–420 Isolating Repeater Level Controller

Dinel IRU–420 Isolating Repeater are designed for supply intrinsically safe level meters in explosive areas and for the conversion of input signal 0/4 ÷ 20 mA to an output signal. Galvanic separation of current signal from explosive area to non-explosive area. The housing of units are made by polycarbonate and ready for mounting on DIN rail 35 mm. Is manufactured in variants for 24 V DC or 230 V AC.

Dinel IRU–420 Isolating Repeater Features

  • Universal intrinsically safe isolating repeater of current signals 0/4 ÷ 20 mA with option voltage output 0 ÷ 10V
  • For supply sensors with output 0/4 ÷ 20 mA in the explosive area
  • Galvanic separation input and output signals
  • Option bidirectional transmission of communication signal HART®
  • Installation on DIN rail 35 mm
  • Variants for 24 V DC or 230 V AC

Electrical Connector

The electrical connection is performed in a voltage-free state. The supply voltage (terminals 13 and 14) can be connected to mains power only via a fuse or a circuit breaker (max. 16 A)! On to terminals 5, 6 and 7 (blue terminal block, side IN) only an approved sensor with a current output of 0/4 … 20 mA may be connected, conforming to the conditions of the given hazardous area. If the sensor is connected to terminals 5 and 6, then it is also powered from these terminals.

If, however, the sensor is connected to terminals 6 and 7, an external power source must be used to power it. The output from the device is a current signal 0/4 … 20 mA or a voltage signal 0 … 10 V with working contacts 9, 10, 11 (grey terminal block, side OUT). Terminals no. 4, 8, and 12, 16 (on version IRU-420-H) are used for the connection of an external communicator HART (HHC – Hand-Held-Communicator).

Dinel IRU–420 Isolating Repeater Specifications

IRU-420-IIRU-420-HIRU-420-U
Input value0/4 … 20 mA0/4 … 20 mA0/4 … 20 mA
Output value0/4 … 20 mA0/4 … 20 mA0 … 10 V (loading max. 20 mA)
Bidirectional transmission communication signal HARTNOYESNO
Nominal supply voltage
variant 230 V60 … 230 V AC (+10 %) 50 ÷ 60 Hz, 85… 230 V DC (+10 %)
variant 24 V18 … 30 V AC (+10 %) 50 ÷ 60 Hz; 18 … 40 V DC (+10 %)
Nominal power demand (AC / DC)7 VA / 4 W
Maximum effective value of AC or DC voltage that can be connected to the terminals follow-up devices that are not intrinsically safe, without breaking the type of protectionUm = 253 V
Voltage on active input (terminals 5 a 6)typ. 24,1 V DC (0 mA) / min. 18 V DC (20 mA)
Output auxiliary voltage (terminals 9 a 11)24 V DC (max. 25 mA)
Linearity? 0,05 % (4 … 20 mA) / ? 0,07 % (0 … 20 mA)? 0,05 %
Temperature error? 0,05 % / K
Allowed short circuit time (input and output)unlimited (short on output is indicated by off LED)
Ambient temperature-20 °C … +60 °C
Protection classIP 20
Housing materialPolycarbonate
Material of terminalsCuBe
Max. conductor size1 x 2,5 mm2
Isolating voltage (main terminals / input + output)3500 V
Isolating voltage (input / output)3500 V
Weightcca 0,2 kg

Download Catalog: ISOLATING REPEATER IRU-420 Dinel-Level and Flow Measurement