TURBISENS Bamo Turbidity Transmitter Immersion Probe

Description

TURBISENS Bamo Turbidity Transmitter Immersion Probe refers to the content of solid particles (example: suspended particles). Designed for open basins or channels, this probe is an immersion turbidity transmitter.  TURBISENS optically measures the turbidity of the liquid. The measurement system complies with standard NF EN ISO 7027 (Nephelometry) The electronics integrated into the head convert the measurement into a 4-20 mA signal.

TURBISENS Bamo Turbidity Transmitter Features

  • Compact transmitter, 4-20 mA output
  • In conformity with EN ISO 7027, infrared light (860 nm), 90ยฐ scattered light
  • Selectable ranges: 0 to 50/ 100/ 200/ 500 / 1000/ 2000 FTU
  • High resolution from 0.01 FTU
  • Max. immersion depth: 10 m

Application

Control and monitoring of

  • Wastewater treatment plant outlets
  • Sedimentation process
  • Wells
  • Cooling water basin

TURBISENS Bamo Turbidity Transmitter Specification

Output signal4-20 mA
Example: Connection to a BAMOWIZ or an
analogue PLC input
Power supply10 โ€ฆ 30 V DC, galvanically isolated from
measuring circuit
Consumption< 1 W
Note:
When the 4-20mA loop is powered by the connected monitor or PLC, the connected load increases by 0.48 W: 24 x 20 = 0.48 (24 V DC; 20 mA; 0.48 W)
Ambient temperature0โ€ฆ +45 ยฐC
Probe protectionIP 68, max. depth 10 m (EN 60 529)
CableTPK, length 6m (special lengths on request),
Connection to head housing via a watertight
connector (IP67).
Resistant to highly diluted acids and alkalis
Liquid temperature0โ€ฆ +60 ยฐC
Probe bodyPVC
Selectable Ranges0 to 50 / 100 / 200 / 500 / 1000 / 2000 FTU
FTU= Formazin Turbidity Units
Accuracyยฑ5 % of reading
ยฑ1 % F.S. in use
ResolutionOr 0.01 FNU or 1 FTU according to the measuring
range
Color compensationColor compensation in the measuring range 50
and 100 FTU
Head housingPBT, IP 65 (EN 60 529)
Fitting2โ€ BSP male; With counter-nut and angle bracket
Display, integrated to the head4 Digits for current turbidity and settings
Status LED for alarm signals
SettingsRotating potentiometer/ push button
OptionTest kit for a quick check of the device.

Download Data Sheet: Turbidity Transmitter, Immersion Probe TURBISENS

Ref: bamo.eu