Onicon F3500 Insertion Electromagnetic Flow Meter
Onicon F3500 Insertion Electromagnetic Flow Meter

Onicon F3500 Insertion Electromagnetic Flow Meter

Description

Onicon F3500 Insertion Electromagnetic Flow Meter are suitable for measuring electrically conductive liquids in a wide variety of applications. Each F-3500 provides a single analog output for flow rate, a high-resolution frequency output to drive peripheral devices, scalable pulse output for totalization, and an empty pipe alarm signal. Two versions of the F-3500 are now available. The standard configuration F-3500 is suitable for pipe sizes ranging from 3” to 72” in diameter. The small pipe configuration F-3500 is suitable for pipes ranging in size from 1¼” to 2½” in diameter. Optional remote displays and BTU measurement systems are also available for both versions.

Onicon F3500 Insertion Electromagnetic Application

  • Accurate, reliable flow measurement for HVAC applications
  • Ideal for monitoring open-loop condenser water flow
  • Hot tap design simplifies domestic water retrofit installations
  • The cost-effective way to monitor flow in larger pipe sizes
  • Suitable for use in water and water/glycol systems

Specification

Accuracy±1.0% of reading from 2 – 20 ft/s
± 0.02 ft/s below 2 ft/s
Flow Range0.1 ft/s to 20 ft/s (200:1 turndown)
Sensor MethodElectromagnetic sensor (no moving parts)
Pipe Size RangeStandard Configuration:3- 72” nominal diameter
Small Pipe Configuration:1¼ – 2½” nominal diameter
Input Power20 – 28 VDC, 250 mA at 24 VDC
20 – 28 VAC, 60 Hz, 6 VA
Temperature Range15°F to 250°F
Ambient Temperature Range-20°F to 150°F
Operating Pressure400 psi maximum
Pressure DropStandard Configuration:0.1 psi at 12 ft/s in 3” pipe, decreasing as line size increases
Small Pipe Configuration:0.33 psi at 8 ft/s in 1.25” pipe, decreasing as the line size increases
Output Signal ProvidedAnalog Output (Isolated)Selectable: 4-20 mA, 0-10 V or 0-5 V
Frequency Output0-15 V peak pulse, 0-500 Hz
Scalable Pulse OutputIsolated solid-state dry contact
Contact rating: 50 VDC, 100 mA maximum
Pulse duration: 0.5, 1, 2 or 6 second
MaterialWetted metal components:316 Stainless Steel
Sensor head:XAREC
Optional:NSF/ANSI 61/372 version
Electronics EnclosureWeathertight NEMA 4 aluminum enclosure
Electrical Connections10’ of PVC jacketed cable with ½” NPT conduit connection
Dedicated earth wire required
4-wire minimum for power and analog output
Additional wires required for pulse, frequency and alarm outputs

Onicon F3500 Insertion Electromagnetic Ordering Information

Meter Model Number Coding= F-35AA-BB-CC-DEFG(-SPC)

F-35

AA = Insertion Electromagnetic Flow Meter

  • 00 = Insertion electromagnetic flowmeter

BB = Outputs

  • 11 = Frequency, isolated analog, scaled pulse and alarm (dry contacts)
  • 12 = Frequency, isolated analog, bi-directional, scaled pulse and alarm (dry contacts)*

CC = Pipe Size Range and Meter Length

  • A1 = 1.25 – 2.5” (F-3500 Small Pipe)
  • C3 = 3.0 – 10.0”
  • D4 = 3.0 – 16.0”
  • E5 = 3.0 – 22.0”
  • F6 = 3.0 – 72”

D = Process Connection

  • 1 = 1” NPT adapter. ?” stem

E = Wetted Material

  • 1 = 316 SS, XAREC, Viton, Temp < 150°F
  • 2 = 316 SS, XAREC, FKM, Temp ? 250°F
  • 3 = 316 SS, XAREC, EPDM, NSF rated for domestic water

F = Electronics Enclosure

  • 1 = NEMA 4 weathertight enclosure

G = Wiring Connection

  • 1 = 10’ PVC jacketed cable, pigtail with ½” conduit adapter

SPC = Special Configuration

*For 3” and larger pipes

Source : www.onicon.com