Description
J Schneider AKKUTEC 4806, The accumulator buffered DC supply works according to the standby parallel principle and guarantees, in connection with a lead accumulator and for a certain time interval, a safe upkeep of the DC supply in case of a mains failure. The overall output current is split up between consumer supply and lead accumulator charge.
The power supply is characterized by the following properties:
- Switching power supply with I/U charging characteristic
- aktiv power factor correction (PFC)
- Micro-controller supported lead accumulator management
- RS232 for monitoring and parameterization
- Temperature adjustment of the charging voltage by an external sensor
J. Schneider AKKUTEC 4806 Technical Data
Nominal input voltage | 230 V AC (±15%) |
Input voltage range for charging operation | 195,5 V … 264,5 V |
Nominal frequency | 47 Hz … 63 Hz |
Power consumption | 380 VA |
Self current consumption | 35 mA @ 48 VDC oder 6,4W @ 230 VAC |
Max. nominal input current | 1,95 A |
Max. inrush current | 35 A / 2 ms |
Max. nominal output current | 6 A |
Nominal output voltage (in mains operation) | 48 V DC |
Output voltage range (with temperature tracking) | 43,2 V … 57,2 V DC ±0,4% |
Charging characteristics | I/U DIN41773 |
Charging end voltage (without Temp.-Sensor) | 52,8 V DC ±0,4% |
Deep discharge protection and load rejection | 40,8 V DC ±0,4% |
Max power loss ‚worst-case‘ | 40 W |
efficiency | 89% @ (Ue=230 V; Ua=52,8 V DC; Ia=INenn) |
Residual ripple | < 150 mV eff. |
Internal device protection | 2,5 A (T), 250 V |
fuse DC-output circuit (external) | 7,5 A (T, UL-248) |
Fuse DC-Battery circuit (external) | 7,5 A (T, UL-248) |
Connection in parallel | Yes |
Conncection in series | no |
Max. signal contact load (Mains-OK2 ) | 60 V/ 0.5 A potential-free relay-contact |
Max. signal contact load (Bat-OK2) | 60 V/ 0.5 A potential-free relay-contact |
Max. signal contact load (General Fault2) | 60 V/ 0.5 A |
Max. signal voltage range (Shut-Down) | 48 V DC (6-45 V DC) |
Accumulator type | Pb-accumulator, maintenance-free, |
Back-up time | Accumulator specific |
Protective system | IP20 |
Operating temperature | -10 °C … 50 °C |
Storage temperature | -10 °C … 50 °C |
Rel. Humidity | ?95% no condensation |
Max. installation altitude | 2000 m above sea level |
Dimensions (HxWxD) | 155 mm, 95 mm, 183 mm |
Weight | 1.5 Kg |
Fixation | Snap-on mounting for DIN top hat rail or mounting bracket for mounting plate |
UL approvals | No |
Reference : j-schneider.de
Download : Datasheet
Other Article:
- J. Schneider AKKUTEC 2403 DC
- J. Schneider AKKUTEC 2403 K
- J. Schneider C-TEC 2440-4 P
- Kracht DT 5 Duo Tec Series – Gear Pump
- J. Schneider NBBH 2401
- J. Schneider C-TEC 1203
- J. Schneider C-TEC 1225 P
- J. Schneider C-TEC 2403 USB
- Kracht KP 1 Duo Tec – Gear Pump Series
- J. Schneider C-TEC 2403-1of
- J. Schneider C-TEC 4815 P
- J. Schneider AC C-TEC 2403-1-400