J. Schneider C-TEC 2410 13.4kJ

J. Schneider C-TEC 2410 13.4kJ Capacitor buffered Power Supply, The DC UPS of the CTEC series has inside of the housing ultracaps as energy storage.
In mains operation, the ultracaps will be charged by an external controlled DC power supply.
In the event of interruption of DC power supply, the energy of the ultracaps will be released in a controlled way. The load will be fed until the C-TEC is discharged.

The buffer time depends on the output current and the energy of the ultracaps.

The C-TEC 2410 is characterized by the following properties:

  • Maintenance-free due to durable ultracaps
  • Micro-controller supported charging and discharging of the ultracaps
  • Operation monitoring and charge status monitoring by LEDs
  • Fast charging by active current charging control
  • IPC management by time triggered and output current triggered shutdown function
  • Numerous customer-specific parametrization settings by USB interface

Another Article:

J. Schneider C-TEC 2410 13.4kJ Technical Data

Input
Nominal input voltage* 12 V DC / 24 V DC (SELV / PELV)
Input voltage range in charge mode 11.9…17.4 V DC ±0 % / 11.4…17.4 V DC ±0 %
23.9…27 V DC ±0 % / 23.4…27 V DC ±0 %
Nominal input voltage 12 V DC (decoupled / non-decoupled)
Nominal input voltage 24 V DC (decoupled / non-decoupled)
Nominal input current 10 A
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 9.9 A
Inrush current ≤ 35 A / 2 ms
Charging current Max. 7 A; active charging current control
Nominal input power 240 W
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 10 A)
Output
Nominal output voltage 12 V DC / 24 V DC
Nominal output voltage in buffer mode (system voltage)** 11.2 V DC ±4 %
23.2 V DC ±2 %
Nominal input voltage 12 V DC
Nominal input voltage 24 V DC
Nominal output current 10 A
Current limitation in discharge operation 11.25 A ±0.75 A
Limiting current monitoring in discharge operation by switching-off 10.3 A ±0,1 A after 1.5 s
Energy capacity (typical) NCPA0606G01 13.4 kJ (kWs) @ (Ua = 23.2 V DC, Ia = 2 A)
Efficiency 95,1 %
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 10 A)
Internal consumption in buffer mode 1.7 W
Short-circuit resistance Mains operation Conditional short-circuit proof
Buffer mode Short-circuit proof
Fuse
Fuse output circuit External
General
Protection class of the housing IP20
Overvoltage category II
Pollution degree 2
Dimensions (H x W x D) 6.78 in x 4.55 in x 5.65 in
(172 mm x 116 mm x 143 mm)
Weight 4.85 lbs (2.2 kg)
Operating temperature / storage temperature -40 °F(-40 °C)…140 °F (+60 °C)
Operating temperature UL tested 50 °F (+10 °C)…140 °F (+60 °C)
Relative humidity ≤95 % non-condensing
Max. height above sea level (without power reduction) 6561.1 ft (2000 m)

Reference : j-schneider.de

Download :Datasheet

Share
%d bloggers like this: