J. Schneider C-TEC 2410 27.6kJ Capacitor buffered Power Supply, The DC UPS of the C–TEC series has inside of the housing ultracaps as energy storage.
In mains operation, the ultracaps will be charged by an external controlled DC power supply.
In the event of interruption of DC power supply, the energy of the ultracaps will be released in a controlled way. The load will be fed until the C-TEC is discharged.
The buffer time depends on the output current and the energy of the ultracaps.
The C-TEC 2410 is characterized by the following properties:
- Maintenance-free due to durable ultracaps
- Micro-controller supported charging and discharging of the ultracaps
- Operation monitoring and charge status monitoring by LEDs
- Fast charging by active current charging control
- IPC management by time triggered and output current triggered shutdown function
- Numerous customer-specific parametrization settings by USB interface
Another Article: |
J. Schneider C-TEC 2410 27.6kJ Technical Data
Input |
|||
Nominal input voltage* |
12 V DC / 24 V DC (SELV / PELV) |
||
Input voltage range in charge mode Nominal input voltage 12 V DC (decoupled / non-decoupled) Nominal input voltage 24 V DC (decoupled / non-decoupled) |
11.9…17.4 V DC ±0 % / 11.4…17.4 V DC ±0 % |
||
Nominal input current |
10 A @ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 9.9 A |
||
Inrush current |
≤ 35 A / 2 ms |
||
Charging current |
Max. 7 A; active charging current control |
||
Nominal input power |
240 W |
||
Output |
|||
Nominal output voltage |
12 V DC / 24 V DC |
||
Nominal output voltage in buffer mode (system voltage)** Nominal input voltage 12 V DC Nominal input voltage 24 V DC |
11.2 V DC ±4 % |
||
Nominal output current |
10 A |
||
Current limitation in discharge operation |
11.25 A ±0.75 A |
||
Limiting current monitoring in discharge operation |
10.3 A ±0,1 A after 1.5 s |
||
Energy capacity (typical) |
NCPA0606G01 |
27,6 kJ (kWs) @ (Ua = 23.2 V DC, Ia = 2 A) |
|
Efficiency |
95,1 % |
||
Internal consumption in buffer mode |
1.7 W |
||
Short-circuit resistance |
Mains operation Buffer mode |
Conditional short-circuit proof |
|
Fuse |
|||
Fuse output circuit |
External |
||
General |
|||
Protection class of the housing |
IP20 |
||
Overvoltage category |
II |
||
Pollution degree |
2 |
||
Dimensions (H x W x D) |
|
6.71 in x 7.44 in x 5.82 in (170 mm x 189 mm x 147,9 mm) |
|
Weight |
|
7.94 lbs (3.6 kg) |
|
Operating temperature / storage temperature Operating temperature UL tested |
-40 °F(-40 °C)…140 °F (+60 °C) 50 °F (+10 °C)…140 °F (+60 °C) |
||
Relative humidity |
≤95 % non-condensing |
||
Max. height above sea level (without power reduction) |
6561.1 ft (2000 m) |