ADEL DPY351 ADELViewgraphic Robust Multifunctional display

General Information

ADEL DPY351 ADELViewgraphic Robust Multifunctional is a robust multifunctional display for managing ADELSystem devices connected in an ADELBus network. It has high brightness and a wide viewing angle of 3.5’’ TFT-LCD. The user interface is clear, intuitive and allows configuring and managing the connected devices in a quick and straightforward way. Using the onboard Ethernet interface, it is possible to remote manage of ADELBus network.
  • It is equipped with a high-brightness and wide viewing-angle 3.5’’ TFT screen which guarantees an optimum visibility in any operating condition.
  • Intuitive Human-Machine Interface (HMI) is a user interface or dashboard clear and intuitive
  • Ethernet interface inside, allows to configure and managing true ADELBus the devices connected through its,  by using the SNMP and Modbus TCP protocols.
  • It is possible to connect several devices in chain together, up to 30.
  • Monitoring: It is possible the monitoring of the input and output data, peak current, peak voltage, all the battery parameters such as temperature, State of Charge internal Impendency
  • Configuration: With the DPY351, it is possible to modify the parameters of any ADELsystem device connected: DC Ups, Power Supply, and Battery Charger.
  • Alarms management: All the alarms present on the single device are immediately reported.
  • History: The history parameters are recorded inside each device. The DPY351 allows inspecting all the historical parameters of every single device.
  • Logging: The device memorizes and displays the last 20 actions done.
  • Web Server: It is possible configure and drive the device by Own Server
  • Event: Actions that are coordinated among the devices connected can be programmed, thus automating the system.

The heart of the easy-to-assemble system is a 90mm hole for all types of surfaces, designed for heavy-duty use in a robust IP67, which allows you to manage multiple units by monitoring, configuring, storing, and connecting remotely. A unique device, the first that allows all the functions to be enclosed inside for maximum performance at the highest levels of ADELSystem devices.

Feature

Through the ADEL DPY351 ADELViewgraphic Bus network (Adel System network)it manages all the connected devices:

Monitoring

ADEL DPY351 ADELViewgraphic is possible the monitoring of the input and output data, peak current, peak voltage, all the battery parameters
such as temperature, State of Charge, etc…

Configuration

With the DPY351, it is possible to modify the parameters of any device connected: DC Ups, Power Supply and Battery Charger.

Alarms management

All the alarms present on the single device are immediately reported.

History

The history parameters are recorded inside each device. The DPY351 allows inspecting all the historical parameters of each single device.

Logging

Actions that are coordinated among the devices connected can be programmed, thus automating the system.

Web server It is possible configure and drive the device by Own Server

Gateway and Protocols

ADELsystem. Main functions:

  • Monitoring
  • Configuration
  • Alarms management
  • History
  • Logging
  • Event

Web Server HTTP for Configuration and Driver the device by Ethernet; static or Dynamic IP Modbus TCP/IP Configuration TCP/IP Configuration group of parameter default values. They allow the unique identification of the unit in the network.

SNMP v2c An ADELsystem MIB table is provided which consists of a list of parameters of the connected power device that can be remotely read, or read-written through the SNMP. Each parameter, (OID), is mapped one-to-one to a Modbus RTU holding register.

MQTTMQTT communication allows the DPY351 to connect to the ADELView System Cloud for the remote monitoring of the power devices connected to the DPY using Modbus or CANbus

Gateway for:

  • Ethernet
  • IIoT (Cloud)
  • CAN Bus
  • MODBUS
  • USB
  • Webserver

ADEL DPY351 Robust Multifunctional Connection & Control

ADEL DPY351 ADELViewgraphic  was developed to connect to all the new devices developed by ADELSystem. Through ADELBus (CANBus and ModBus) it is possible to establish the connection of configuration, reading, evolution of the device data. Through the DPY351 it is possible to create Events, they are the result of an algorithm established by the DPY351 among the various interconnected devices.

Interactive functions

Opens the head to ADELSystem devices. View, control, integrate PLC functions and transmit all system functions via Ethernet. Compact, user-friendly, high performance, it’s the device you never thought of, but now that it’s there and you will not be able to do without it.

Technical Data

Input Data

  • DC Input Voltage range (Vdc)  : 9-72
  • Power from Aux3 :  Yes
  • Current consumption ON typ. (backlight 30%, MODBUS* on, relay off)
    • 0.13A (12VDC, Ethernet off)
    • 0.17A (12VDC, Ethernet on)
    • 0.08A (24VDC, Ethernet off)
    • 0.1A (24VDC, Ethernet on)
  • Current Consumption (Out6 Switch4 pos. OFF) : 0 mA
  • Maximum current consumption with backlight 100% :
    • 0.32A (9VDC, MODBUS*, Ethernet and relay on)
    • 0.10A (72VDC, MODBUS*, Ethernet and relay on)
  • Maximum current consumption with backlight 0% :
    • 0.22A (9VDC, MODBUS*, Ethernet and relay on)
    • 0.07A (36VDC, MODBUS*, Ethernet and relay on)
  • Current Consumption in Sleep mode :  < 1 mA
  • External Fuse (recommended) :  1A slow-blow

Display Screen

  • Type : TFT LCD display, 16bit color (64k colors)
  • Resolution : 320 x 240 pixels 3.5 Inch
  • Brightness : 800 cd/m2
  • Orientation : Landscape
  • Backlight (life time) : LED, white (>20000h)

Data Connection

  • Aux1 Input temperature sensor :  ADELSystem RJ Temp temperature probe
  • Aux2 Ethernet : 10/100M. VLAN is supported.
  • Protocols: SNMP, DHCP, MODBUS TCP, HTTP webserver
  • Aux3: CAN Bus SAE J1939
  • Aux3: RS485 : MODBUS lines fully loaded with 32 unit loads and terminated at both ends with 120-ohm resistors. MODBUS RTU
  • Data lines termination :  120 ohm for RS485, 120 ohm for CAN bus individually activated with user-accessible dipswitches
  • Data lines polarization Yes, RS485 lines only to supply rails, individually activated with useraccessible dipswitches
  • Aux4: USB: 2.0 device, full speed 1 x USB B connector
  • Keyboard 4 tactile buttons, backlit

Ambient Conditions

  • Ambient Temperature operation -25 up to +70 °C
  • Ambient Temperature Storage -40 up to +85 °C
  • Humidity at 25 °C, no condensation 95 % to 25 °C
  • Vibration (operation) IEC 60068-2-6 <15 Hz, amplitude ± 2.5mm<15Hz-150Hz, 2.3G 90 min.
  • Shock IEC 60068-2-6 30g in all directions

General Data

  • Protection Class  (EN/IEC 60529) :  IP20; Front panel only IP65
  • Reliability: MTBF IEC 61709 > 200.000 h
  • Connection Terminal Blocks Screw Type : 0.08-1.31 mm2 (24 – 16 AWG)
  • Protection class : II
  • Housing material : Polycarbonate
  • Foot latch material : Plastic POM
  • Dimension (w-h-d) mm:  112 x 115 x 52
  • Weight 0.35 kg approx.
  • Hole 90 mm
  • Available Languages English
  • Automatic Power ON By setting Deep Switch (Aux6)
Reference: adelsystem.com