Description
J. Schneider CAPTEC 2410 Capacitor Buffered Power Supply, The DC-UPS of the series CAPTEC includes ultra-capacitors as energy storage inside the housing. This capacitor is charged with the system voltage during normal operation.
The connected loads are supplied as well from the system voltage. In case of an interruption of the system voltage the energy of the ultra-capacitors is released in a regulated way. With a DC/dc converter, the load is supplied by the capacitor until it is discharged. The backup time depends on the state of charge of the capacitor and the discharge current.
The DC-UPS has the following characteristics:
- Maintenance-free because of long-life ultra-capacitors
- Microcontroller-based charging and discharging of the ultra-capacitors
- Parameterizable via USB interface with the TECControl-Software
- Control of operation and status of charge with LEDs and signal contacts
J. Schneider CAPTEC 2410 Technical Data
Input | |
Nominal input voltage | 12 V DC / 24 V DC |
Input voltage range | 11,4 V DC – 27 V DC |
Nominal input current | 10,0 A |
Max. inrush current | 35 A / 2 ms |
Energy1 @ Iout= 2 A | 14 kJ ±4 % |
Minimum charging voltage | System voltage + 0,2 V DC |
Output | |
Output voltage in backup operation (System voltage) | 11,2 V DC ±4 % |
Nominal voltage 12 V | 23,0 V DC ±2 % |
Nominal voltage 24 V | |
Nominal output current | 10 A |
Monitoring of limiting current | 10,3 A ±0,1 A |
Switch off if limiting current is exceeded | after 1,5 s |
Current limitation (in back-up operation) | 1,05…1,2 x IoutNom |
Efficiency in mains operation (if capacitors are charged) @ Iout= 10 A | 98 % |
power loss in mains operation (if capacitors are charged) @ Iout= 10 A | 5,4 W |
Power loss in charge and discharge operation | 20 W |
Fuse | |
Fusing input | 15 A (FK2) (device internal) |
Fusing DC-output circuit | 15 A (FK2) (device internal) |
Fusing DC-output circuit | 25 A (FK2) (device internal) |
Overall | |
Type of connection input IN X1(1, 2) | Spring-clamp technique |
Type of connection output OUT X1(3, 4, 5) | max. 6,0 mm² (AWG 24-10) |
Type of connection messages SD X3(1, 2), IN OK X3(3, 4), REL X2(1, 2, 3) | Spring-clamp technique |
max. 2,5 mm² (AWG 24-12) | |
Type of connection USB X4 | USB-B socket |
Protective system | IP20 |
Dimensions (H x W x D) | 4.86 in x 6.5 in x 5.96 in |
(124 mm x 165 mm x 151 mm) | |
Weight | 2,0 kg |
Storage temperature / environmental temperature | -40 °C…+60 °C |
Humidity | 95 % condensation is not permissible |
1 in new condition of the device at 25 °C ambient temperature
Reference: j-schneider.de
Download: Datasheet
Other Article:
- J. Schneider C-TEC 2440-4 P
- Fcon CUBE GM-X? series Touch Panel Gas Mixer with Buffer tank
- J. Schneider C-TEC 1203
- J. Schneider C-TEC 2403-1of
- J. Schneider C-TEC 2410 2kJ
- J. Schneider NBBH 2401
- J. Schneider C-TEC 1203
- J. Schneider C-TEC 1225 P
- J. Schneider C-TEC 2403 USB
- Kracht KP 1 Duo Tec – Gear Pump Series
- J. Schneider C-TEC 4815 P
- J. Schneider AC C-TEC 2403-1-400