J. Schneider CAPTEC 2410

Description

J. Schneider CAPTEC 2410 Capacitor Buffered Power Supply, The DC-UPS of the series CAPTEC includes ultra-capacitors as energy storage inside the housing. This capacitor is charged with the system voltage during normal operation.

The connected loads are supplied as well from the system voltage. In case of an interruption of the system voltage the energy of the ultra-capacitors is released in a regulated way. With a DC/dc converter, the load is supplied by the capacitor until it is discharged. The backup time depends on the state of charge of the capacitor and the discharge current.

The DC-UPS has the following characteristics:

  • Maintenance-free because of long-life ultra-capacitors
  • Microcontroller-based charging and discharging of the ultra-capacitors
  • Parameterizable via USB interface with the TECControl-Software
  • Control of operation and status of charge with LEDs and signal contacts

J. Schneider CAPTEC 2410 Technical Data

Input
Nominal input voltage12 V DC / 24 V DC
Input voltage range11,4 V DC – 27 V DC
Nominal input current10,0 A
Max. inrush current35 A / 2 ms
Energy1 @ Iout= 2 A14 kJ ±4 %
Minimum charging voltageSystem voltage + 0,2 V DC
Output
Output voltage in backup operation (System voltage)11,2 V DC ±4 %
Nominal voltage 12 V23,0 V DC ±2 %
Nominal voltage 24 V
Nominal output current10 A
Monitoring of limiting current10,3 A ±0,1 A
Switch off if limiting current is exceededafter 1,5 s
Current limitation (in back-up operation)1,05…1,2 x IoutNom
Efficiency in mains operation (if capacitors are charged) @ Iout= 10 A98 %
power loss in mains operation (if capacitors are charged) @ Iout= 10 A5,4 W
Power loss in charge and discharge operation20 W
Fuse
Fusing input15 A (FK2) (device internal)
Fusing DC-output circuit15 A (FK2) (device internal)
Fusing DC-output circuit25 A (FK2) (device internal)
Overall
Type of connection input IN X1(1, 2)Spring-clamp technique
Type of connection output OUT X1(3, 4, 5)max. 6,0 mm² (AWG 24-10)
Type of connection messages SD X3(1, 2), IN OK X3(3, 4), REL X2(1, 2, 3)Spring-clamp technique
max. 2,5 mm² (AWG 24-12)
Type of connection USB X4USB-B socket
Protective systemIP20
Dimensions (H x W x D)4.86 in x 6.5 in x 5.96 in
(124 mm x 165 mm x 151 mm)
Weight2,0 kg
Storage temperature / environmental temperature-40 °C…+60 °C
Humidity95 % condensation is not permissible

1 in new condition of the device at 25 °C ambient temperature 

Reference: j-schneider.de