Bamo MAXITOP LW C Level Leak Detector is designed to detect the presence of liquids (acids, alkalis) with a reactance below 5 kOhm and a coupling capacitance towards ground of more than 50 pF. In no case should liquids form insulating or conductive deposits.
Bamo MAXITOP LW C Features
- Capacitance detection loop
- For aggressive and conductive liquids
- Fail safe; Auto-diagnostic with SHR relay
- Wet parts in plastic materials
- Safe: no electrode touching the fluid
The MAXITOP LW C has 4 different possible interfacing connections
- Direct connection to a 4 channels alarm unit MAXIMAT TC4 or 1 channel unit MAXIMAT TC1
- Direct connection to a PLC
- For relay output and loop diagnostic with a MAXIMAT SHR
- For relay output with a MAXIMAT CST
Application
With its integrated positive safety converter, the MAXITOP is ideal to give an alarm when a leakage occurs from storage tank for electrically conductive, non-flammable liquids, even highly aggressive liquids.
Bamo MAXITOP LW C Specification
Power supply | 15 … 27 V DC |
Consumption | < 1 W |
Operating pressure | Atmospheric 0.8 to 1.1 bar |
Probe | HD-PE, O.D. 40 or 25 mm |
Suspension cable | Shielded cable, PVC sheath, standard length 6 m, |
5-wire, 0.34 mm² | |
Head housing | PBT, fiber glass reinforced, |
IP 65 according EN 60 529 | |
Connectors | Screw terminals, wire Max. 2.5 mm² |
Input | For external button switch to test the complete system |
Signaling display | Green LED on the terminals board |
Output | Reed contact, potential free, for low voltage |
Rated: 50 V AC/DC; 0.5 A; 10 VA | |
Hysteresis | About 2 mm |
Switching contact | Liquid height Min. 5 mm |
Download Data Sheet: Level Leak Detector MAXITOP LW C