J. Schneider AKKUTEC 19-2420 1ph

General Information

J Schneider AKKUTEC 19-2420 1ph, The battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.

The power supply has the following features:

  •  Primary switched power supply with I/U-charging characteristics
  • active power factor correction (PFC)
  • Battery management by micro-controller
  • Battery voltage tracking of the charging voltage by external sensor module (optional)
  • Display- and control panel for mount in cabinet door or module (optional)

Display- and control panel for mount in cabinet door or module (optional)

J Schneider AKKUTEC 19-2420 1ph Technical Data

Input voltage range 

230V AC -15/+10%

Rated input current:

2,7A AC

Input frequency

47-63Hz

max. inrush current

65A / 3ms

Ouptut voltage

a) 19…26,4V DC

b) 19…28,6V DC
(if boost charging is activated respectively at temperature tracking)

Final charging voltage

26,4V DC ±0,4%

Charging characteristics

I/U DIN 41773-1

Deep discharge protection and load rejection at

19,8V DC ±0,4%

Nominal output current

20A DC

Constant current limitation

1,05…1,1xIANom

Battery type

Pb-Akku, wartungsfrei

efficiency

Ua=26,4V DC, Ia=20A und Ue=230V AC

88,8%

max. power loss ‘worst-case’

82W

Earth leackage current

<3,5mA

Fusing primary

5A slow acting, 5×20 (internal)

max. pre-fusing

10A slow acting

fusing battery load circuit

25A slow acting (external)

fusing DC-output

25A slow acting (external)

Type of connection primary ‘mains’

Combicon-screw type terminal 2,5mm2

Type of connection sekundary  ‘Ua’, ‘Batt’

Combicon-screw type terminal 4mm2

Type of connection interface ‘IO-1…IO-3’

Combicon-screw type terminal 1,5mm2

Type of connection Current-Share-Bus ‘CS’

Screw type terminal 2,5mm2

Display and messages

‚Netzbetrieb‘ operation

LED green illuminates:

·  Mains operation
(UE>UEmin and TInt<TIntmax)

LED green
(battery voltage within the monitoring window 21,6< UBatt < 27V DC)

LED green
(battery voltage above the monitoring window UBatt  =27V DC

Fehler (fault)

LED red
LED illuminates at:

· Battery operation (during mains operation LED is not illuminated)

· UA– error

· Battery circuit interrupted respective high-ohmic (Testintervall 60s)

· Battery low

· Battery reverse poled

· Battery-over-temperature (only in connection with temperature tracking

Signal in- and outputs

Mains operation 1)

potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

Fehler 1)

potentialfree relay-contact, changer, max. contact load 30 V DC/ 0,5A

 1)

potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

 1)

potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

Shut-Down

Shut down of UPS mode

Switch input, referring ot earth, switch level: 24V DC (16-80V DC)

Starkladung (Boost charging)

Activation of boost charging (boost charging voltage 28.6V DC)
Switched input referenced to earth, switching level: 24V DC (16-80V DC)

Weight

b)19 “ – version

ca. 6,0 kg

Storage Temperature

Recommended 0…30°C,
Permissible 0…50°C

Operating Temperature

Recommended 10…20°C (battery life!),

Permissible 0…40°C

Protective system

IP20

dimensions

19“ Rack482,6 x 132,5 x 244 mm (W x H x D)
UL approvalsNo

Reference : j-schneider.d