J Schneider AKKUTEC 2412 VdS, The battery buffered DC power supply is working according to the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply during a determined time interval in case of mains failure. The total output current is shared between the supply of the loads and charging of the batteries.
Another Article: |
J. Schneider AKKUTEC 2412 VdS Technical Data
Nominal input voltage |
230 V AC (±15%) |
Input voltage range for charging operation |
195.5 V … 264.5 V |
Nominal frequency |
47 Hz … 63 Hz |
Power consumption |
380 VA |
Self current consumption |
75 mA @ 24 V |
Max. nominal input current |
1.8 A |
Max. inrush current |
35 A / 2 ms |
Max. nominal output current |
12 A |
Nominal output voltage (in mains operation) |
24 V DC |
Output voltage range (with temperature tracking) |
26.4 V … 28.6 V DC ±0.4% |
Charging characteristics |
I/U DIN41773 |
Charging end voltage (without Temp.-Sensor) |
26.4 V DC ±0.4% |
Deep discharge protection and load shedding |
20.4 V DC ±0.4% |
Max power loss ‚worst-case‘ |
40 W |
Efficiency |
89% @ (Ue=230 V; Ua=26.4 V DC; Ia=INenn) |
Voltage ripple |
< 150 mV eff. |
Internal device protection |
2.5 A (T), 250 V |
Fuse DC-output circuit (external) |
15 A(T) |
Fuse DC-Battery circuit (external) |
15 A(T) |
Connection in parallel |
Yes |
Connection in series |
Yes |
Max. signal contact load (Mains-OK1 ) |
30 V/ 0.5 A potential-free relay-contact |
Max. signal contact load (Bat-OK1) |
30 V/ 0.5 A potential-free relay-contact |
Max. signal contact load (General Fault1) |
30 V/ 0.5 A |
Max. signal voltage range (Shut-Down) |
24 V DC (6-45 V DC) |
Accumulator type |
Pb-accumulator, maintenance-free, max. 170 Ah |
Back-up time |
Accumulator specific |
Protective system |
IP20 |
Operating temperature |
-10 °C … 50 °C |
Storage temperature |
-10 °C … 50 °C |
Rel. Humidity |
≤95% no condensation |
Max. installation altitude |
2000 m above sea level |
Dimensions (HxWxD) |
155 mm, 95 mm, 183 mm |
Weight |
1.5 Kg |
Fixation |
Snap-on mounting for DIN top hat rail or mounting bracket for mounting plate |
Ul approvals |
UL 508 C22.2 |
Reference : .j-schneider.de
Download : Datasheet
You must be logged in to post a comment.