J. Schneider C-TEC 2410 13.4kJ

Descriptions

J. Schneider C-TEC 2410 13.4kJ Capacitor buffered Power Supply, The DC UPS of the CTEC series has inside of the housing ultracaps as energy storage. In mains operation, the ultracaps will be charged by an external controlled DC power supply.

In the event of interruption of DC power supply, the energy of the ultracaps will be released in a controlled way. The load will be fed until the C-TEC is discharged.

The buffer time depends on the output current and the energy of the ultracaps.

The C-TEC 2410 is characterized by the following properties:

  • Maintenance-free due to durable ultracaps
  • Micro-controller supported charging and discharging of the ultracaps
  • Operation monitoring and charge status monitoring by LEDs
  • Fast charging by active current charging control
  • IPC management by time triggered and output current triggered shutdown function
  • Numerous customer-specific parametrization settings by USB interface

J. Schneider C-TEC 2410 13.4kJ Technical Data

Input
Nominal input voltage*12 V DC / 24 V DC (SELV / PELV)
Input voltage range in charge mode11.9…17.4 V DC ±0 % / 11.4…17.4 V DC ±0 %
23.9…27 V DC ±0 % / 23.4…27 V DC ±0 %
Nominal input voltage 12 V DC (decoupled / non-decoupled)
Nominal input voltage 24 V DC (decoupled / non-decoupled)
Nominal input current10 A
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 9.9 A
Inrush current? 35 A / 2 ms
Charging currentMax. 7 A; active charging current control
Nominal input power240 W
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 10 A)
Output
Nominal output voltage12 V DC / 24 V DC
Nominal output voltage in buffer mode (system voltage)**11.2 V DC ±4 %
23.2 V DC ±2 %
Nominal input voltage 12 V DC
Nominal input voltage 24 V DC
Nominal output current10 A
Current limitation in discharge operation11.25 A ±0.75 A
Limiting current monitoring in discharge operation by switching-off10.3 A ±0,1 A after 1.5 s
Energy capacity (typical)NCPA0606G0113.4 kJ (kWs) @ (Ua = 23.2 V DC, Ia = 2 A)
Efficiency95,1 %
@ (Ue = 24.0 V DC, Ua = 23.2 V DC, Ia = 10 A)
Internal consumption in buffer mode1.7 W
Short-circuit resistanceMains operationConditional short-circuit proof
Buffer modeShort-circuit proof
Fuse
Fuse output circuitExternal
General
Protection class of the housingIP20
Overvoltage categoryII
Pollution degree2
Dimensions (H x W x D)6.78 in x 4.55 in x 5.65 in
(172 mm x 116 mm x 143 mm)
Weight4.85 lbs (2.2 kg)
Operating temperature / storage temperature-40 °F(-40 °C)…140 °F (+60 °C)
Operating temperature UL tested50 °F (+10 °C)…140 °F (+60 °C)
Relative humidity?95 % non-condensing
Max. height above sea level (without power reduction)6561.1 ft (2000 m)

Reference : j-schneider.de

Download :Datasheet

Other Article:

Similar Posts